beautypg.com

Fulton VMP Webster Oil_Combo Burner User Manual

Page 35

background image

Combination burners, firing both gas and oil, require some

compromises in the setup because they share common con-

trols for both fuels. In this case, linkage units must have the

gas input adjusted to match the oil inputs because there is

little flexibility in adjusting the oil rates. Oil will be setup first

and will set the air damper positions to support the low and

high fire oil inputs. Follow the procedure outlined in section

11 to complete the oil setup. Then setup the gas input as

defined in section 10, using the air damper positions defined

by oil, and adjusting the gas input to match the air damper

settings.
If the burner is equipped with an optional multiple set-point

modulating motor or parallel positioning, the low and high

fire rates, as well as lightoff rates, can be set independently

for each fuel. In this case, the gas is adjusted first, to set the

air damper locations for gas firing, as defined in Section 10.

Once gas is set, oil is setup as defined in Section 11, except

that the multipoint modulating damper motor is adjusted to

bring the low fire air setting to match the oil needs.
There are several different options available that can alter

the exact setup details, and these must be evaluated prior

to startup so that the procedures can be adjusted accord-

ingly. The procedures given are for linkage systems. Par-

allel positioning (linkageless) systems allow for much more

flexibility in the fuel, air and FGR settings on each fuel, and

can be tuned to better match each fuels needs. The setup

details for linkageless controls will follow the same general

sequence, but differ in specifics for setting the valve posi-

tions.
8. Combination Gas and Air Atomized #2 Oil
Combination burners, firing both gas and oil, require some

compromises in the setup because they share common con-

trols for both fuels. Air atomized #2 oil firing can have turn-

downs and air damper positions very similar to gas firing,

simplifying the setup. If the burner is equipped with FGR,

gas must be started first to set the FGR control valve po-

sitions to obtain the correct NOx performance. If there is

no FGR, either fuel can be started first, however the setup

cannot be finalized until both fuels have been reviewed to

determine the air damper positions. Follow the setup proce-

dures defined in Section 10 for gas setup and Section 12 for

air atomized oil setup.
If the burner is equipped with an optional multiple set-point

modulating motor, the low and high fire rates, as well as ligh-

toff rates, can be set independently for each fuel. In this

case, the gas is adjusted first, to set the air damper locations

for gas firing, as defined in Section 10. Once gas is set, oil

is setup as defined in Section 12, except that the multipoint

modulating damper motor is adjusted to bring the low fire air

setting to match the oil needs.
There are several different options available that can alter

the exact setup details, and these must be evaluated prior

to startup so that the procedures can be adjusted accord-

ingly. The procedures given are for linkage systems. Par-

allel positioning (linkageless) systems allow for much more

flexibility in the fuel, air and FGR settings on each fuel, and

can be tuned to better match each fuels needs. The

setup details for linkageless controls will follow the same

general sequence, but differ in specifics for setting the

valve positions.
9. Combination Gas and Heavy Oil
Combination burners, firing both gas and oil, require

some compromises in the setup because they share

common controls for both fuels. Heavy oil burners can-

not operate with FGR and do not have this adjustment.

If the burner does not have a multiple setpoint modu-

lating motor or linkageless control, oil must be set first,

as the air damper positions will be determined by this

setup. With the multiple setpoint modulating motor, gas

must be set first, as it will dictate the damper positions.

In either case, setup cannot be finalized until both fuels

have been reviewed to determine the air damper posi-

tions. Follow the setup procedures defined in Section

10 for gas setup and Section 13 for air atomized heavy

oil setup.
There are several different options available that can al-

ter the exact setup details, and these must be evaluated

prior to startup so that the procedures can be adjusted

accordingly. The procedures given are for linkage sys-

tems. Parallel positioning (linkageless) systems allow

for much more flexibility in the fuel, air and FGR settings

on each fuel, and can be tuned to better match each fu-

els needs. The setup details for linkageless controls will

follow the same general sequence, but differ in specifics

for setting the valve positions.
10. Gas Setup
a.
Place the burner switch in the “OFF” position

b. Place the “Auto-Manual” switch in the manual posi-

tion, for modulation or low fire hold, switch in low fire po-

sition for Lo-Hi-Lo operation. If this is a combination fuel

burner, make sure the fuel selector switch is on “GAS”.

c. Place the manual flame control potentiometer in the

MIN (low fire) position on modulating units.

d. Close the downstream manual shutoff valve (closest

to the burner head) on the gas train.

e. Turn the electrical power on for the burner, boiler and

related components.

f. Verify that the gas metering valve is nearly closed, the

vent valve (if equipped) is operating and the gas pilot

valve is not open (the solenoid will hum and feel warm).

g. If equipped with FGR, verify that the FGR control

valve is in the near closed position. A linkage system

should have the shutoff FGR valve in the closed posi-

tion.

h. Turn the burner switch on. This will start the blower

motor and initiate the prepurge cycle.

i. When the prepurge sequence is complete and the

low fire start switch (if used) is made, the pilot valve will

open and the pilot flame should be visible through the

sight port.

j. When the pilot flame is established, the flame safe-

guard will energize the main gas valve (indicated with

the Fuel Valve Light). This operation of the main fuel

Page 35

JB Manual

Startup and Operating Adjustments