beautypg.com

Micromod Micro-DCI: 53SL5100B Single Loop Controller User Manual

Page 9

background image

53SL5100B Single-Loop Controller
INSTRUCTION MANUAL

Item

Specification(s)

Environmental Characteristics

Controlled Environment

Enclosed temperature controlled location (Class A and B per ISA-
S71.01 1985)

Ambient Temperature Limits

4 -52°C (40 - 125°F)

Relative Humidity Limits

10 - 90% maximum

Temperature Effects on Accuracy

± 0.28% per 28°C (50°F) change from reference temperature 25°C
(77°F)

Transient Immunity (all circuits)

ANSI C37.90a - 1974/IEEE Std 472-974: Ring Wave: 1.5 MHz, 3 kV,
60 pulses/s for 2.0 s

EMI Susceptibility

SAMA PMC 33.1-1978: Class 3-abc: no effect at 30 V/m, at 27, 146,
and 446 MHz

Enclosure Classification/Environment

Panel Mounted Equipment: No enclosure rating. Designed to be
installed in a user provided panel or enclosure.
Rated for installation in a Pollution Degree 2 location per U.L. 508-
1989/Controlled Environment per CSA C22.2 No. 142-M1987. An
indoor, temperature controlled location (Control Room or Shop Floor)
where normally, only non-conductive pollution occurs; however,
temporary conductivity caused by condensation may be expected.
Location in environments more severe than those stated requires
supplementary protection

Shock 0.5g
Vibration

SAMA PMC 31.1-1978; point-to-point constant displacement 0.05 in.
(1.27 mm), 5 -14 Hz: 0.5 g, 14 - 200 Hz.

Drop and Topple

SAMA PMC 31.1-1978; Tilt 30 degrees from horizontal and fall freely
to a hard surface, all sides, front and back.

Safety Classification

General Purpose: Complies with ANSI/ISA S82.01-1988, Safety
Standard for Electrical and Electronic Test Measuring, Controlling and
Related Equipment; General Requirements and S82.03-1988 Safety
Standard for Electrical and Electronic Test, Measuring, Controlling and
Related Equipment; Electrical and Electronic Process Measurement
and Control Equipment.
FM Approved: Nonincendive for Class 1, Division 2, Groups A, B, C, &
D, Temperature Code T3C 160 ° C.

Physical Characteristics

Material of Construction:

Case

Steel, black enamel

Circuit Boards

Glass epoxy

Bezel

ULTEM 1000 (Polyethermide Resin) Flammability-UL94 5V

Dimensions

2.844W x 5.656H x 12.906L (inches) 73W x 144H x 329L (mm)

Flush Panel Mounting

0.125 inch - 1 inch thickness (3.2 mm - 25.4 mm)

Electrical Connections

Screw type terminal block at rear of casework

Weight

5 lbs (2.3 kg)

Front Panel Display

96 x 48 dot addressable

Front Panel Push Buttons

10 membrane type switches

3