53SL5100B Single-Loop Controller

INSTRUCTION MANUAL

2 PA1n: high when PV> PL1

PA2n: not affected

3 PA1n: not affected

PA2n: low when PV< PL1

low when PV< PL1

ev > PL1

ev < PL2

4 PA1n: high when PV> PL1

PA2n: hi-hi when PV> PL2

5 PA1n:

PA2n: lo-lo when PV< PL2

6

PA1: Hi-Dev when D

PA2: Lo-Dev when D

Alarm Examples:

B335 PV

PL1

(C103)

PL2

(C104)

Alarm

Setpoint Notes

0

>60

60

HIGH

a

> 60 = HIGH alarm

Al rm Llimit 1 is set for 60: PV

0

<40

40

LOW

a

= LOW alarm

Al rm Limit 2 is set for 40: PV < 40

2

>60

60

HIGH

Limit 1 is set for 60: PV > 60 = HIGH alarm

Alarm

2

<40

40

N/A

Alarm Limit 2 is set for 40: PV < 40 = no alarm

3

>60

60

N/A

Alarm Limit 1 is set for 60: PV > 60 = no alarm

3 <40

40 LOW

Low Alarm Limit 2 is set for 40: PV < 40 = LOW
alarm

4

>60

60

HIGH

Alarm Limit 1 is set for 60: PV > 60 = HIGH alarm

4

<70

70

HI- HI

Alarm Limit 2 is set for 70: PV > 70 = HI-HI alarm

5

>40

40

LOW

Alarm Limit 1 is set for 40: PV < 40 = LOW alarm

5

<30

30

LO-LO

imit 2 is set for 30: PV < 30 = LO-LO alarm

Alarm L

6

>50

10

HI-DEV

40

Alarm Limit 1 is set for 40: PV < 40 = HI-DEV alarm

6 <30

-10 LO-DEV 40

larm

Alarm Limit 2 is set for 30: PV < 30 = LO-DEV
a

Analog Output
(Display Only)

ANO0

C00

0

The v
output to be generated by hardware (e.g., 100 % output =
20 m

0

alue in this datapoint represents the percent of

A).

Process Variable

PV

C100

0

lgor

This is the actual PV variable of the controller PID
a

ithm. It is obtained from ANI0.

S

oint

SP

C1

0

his i

ed

decrease pushbuttons or from

etp

01

T
from the setpoint increase/

s the actual setpoint of the PID algorithm obtain

Remote Setpoint (RSP).

Output

OUT

C102

0

hm; otherwise, it is the value determined by

When in Auto, this is the actual result of the controller
PID algorit
the output pushbuttons. it is transferred to ANO0.

Alarm Limit 1

PL1

C103

100

ring units at which

This parameter is the point in enginee
the upper alarm is triggered.

Alarm Limit 2

PL2

C104

0

.

This parameter is the point in engineering units at which
the lower alarm is triggered

Alarm Dead Band

ea

ADB

C105

2

This parameter sets the activation/deactivation gap for
the alarm. This value in engineering units defines an ar
of hysteresis at the alarm point.

Proportional Band

ional action. It modifies the

PB

C106

100

This parameter is the percent of error required to move
the output full scale for proport

104