beautypg.com

Table 4-8. control module (continued) – Micromod Micro-DCI: 53SL5100B Single Loop Controller User Manual

Page 39

background image

53SL5100B Single-Loop Controller

INSTRUCTION MANUAL

33

Table 4-8. Control Module (continued)

Purpose: The primary purpose of this module is to set the instrument’s Alarm Index mode, Alarm
Limits 1 & 2, and Alarm Dead Band.

Title

Symbol

CS

1 | 2 | 3 | 4

CON-0

Datapoint

Default

Attribute

Control Action

RSW

 

106 0

When set to a 0, the controller output increases as
the process value increases.
When set to a 1, the controller output decreases as
the process value increases.

Reverse Valve

RSV

 

L109 0

This parameter provides information for the control
display to indicate which direction the control output
must go to close the final control element. A 1
indicates that 20 mA closes the valve. A 0 indicates
that 20 mA opens the valve.

Manual
Fallback
Disable

MFD

  

L120 0

Under normal operation, whenever the controller is
powered up, the Auto/Manual Selector is forced to
the Manual position. When this datapoint is set to a
1, the selector will not be forced to the Manual
position at power up but will remain in the last
position before power was removed.

Alarm Limit 1

PL1

  

C103 100

Alarm Limit 2

PL2

  

C104 0

These parameters are the points in engineering
units at which the alarms are triggered.

Alarm
Dead
Band

ADB

  

C105 2

This parameter sets the activation/deactivation gap
for the alarm. This value in engineering units
defines an area of hysteresis at the alarm point.

Proportional
Band

PB

 

C106 100

This parameter is the percent of error required to
move the output full scale for proportional action. It
modifies the controller response in standard PID
terms.

Reset Time

TR

 

C107 0

This parameter represents the number of minutes
per repeat of integral action. It modifies the
controller response in standard PID terms.

Rate Time

TD

 

C108 0

This parameter value represents the minutes that
proportional action is advanced (derivative action).

Manual Reset

MR

 

C111 50

This parameter determines the position of the valve
(output) when the instrument is in Automatic mode
and the error is zero. (It is only in effect when TR =
0.)

Controller
Span

  

C115 1100

Controller
Lower Range

  

C116 0

These two parameters set the upper and lower
values on the controller display. They permit the
control action to be defined over a range
independent of the process variable input range.
They also determine the speed at which the
setpoint changes when the up or down arrow
pushbuttons are pressed (CS1 through CS3). For
CS4, they determine only the displayable range, as
the setpoint pushbuttons are not used.

Control Tag
Name

  

A000

An assignable 10 character name that appears with
CS1-4 displays.

Engineering
Units

  

A001 Percent

The default is PERCENT, but is assignable as units
of measure the Process Variable represents.

NOTE: CS1 = Single Loop (PID) Controller, CS2 = Analog Backup Controller, CS3 = Ratio

Controller, and CS4 = Automatic/Manual Station.