Table 4-9. parameter display module – Micromod Micro-DCI: 53SL5100B Single Loop Controller User Manual
Page 40
53SL5100B Single-Loop Controller
INSTRUCTION MANUAL
Table 4-9. Parameter Display Module
Purpose: This module provides quick pushbutton display access to any three selected datapoints (e.g.,
Alarm Limits 1 & 2 and Alarm Dead Band) without the necessity of entering Engineering mode and
addressing the datapoints.
Title
Symbol
PAR1 Default Attribute
Title
PTAG
A014
CON-0
TUNE
This is an assignable in character name that appears
with the parameter display.
Point 1 Name
PNA
A015
PROP.
BAND
This is an assignable 10 character name for the Point
1 Designator.
Point 2 Name
PNB
A016
RESET
This is an assignable 10 character name for the Point
2 Designator.
Point 3 Name
PNC
A017
RATE
An assignable 10 character name for the Point 3
Designator
Point 1 Designator
PDA
F087
C106
value
A database datapoint whose contents will be
displayed under the Point 1 Name (e.g., C103 to
display the Alarm Limit 1 setting).
Point 2 Designator
PDB
F088
C107
value
A database datapoint whose contents will be
displayed under the Point 2 Name (e.g., C104 to
display the Alarm Limit 2 setting).
Point 3
PDC
F089
C108
A database datapoint whose contents will be
displayed under the Point 3 Name (e.g., C105 to
display the Alarm Dead Band).
Modify Disable
PMD
L313
0
When this value is 1, the datapoints in this module can
not be altered with the pushbuttons. The values of
these datapoints are only for display purposes. When
this value is 0, the datapoints in this module can be
altered by the operator with the pushbuttons when this
module is displayed.
34