beautypg.com

2 specifications, Pecifications – Micromod Micro-DCI: 53SL5100B Single Loop Controller User Manual

Page 8

background image

53SL5100B Single-Loop Controller

INSTRUCTION MANUAL

1.2 Specifications

Item

Specification(s)

Power

Range (as specified in model number)

22 - 26 V dc
108 - 132 V rms
216 - 264 V rms
50/60 Hz

Power Consumption (ac/dc operation)

36 VA maximum

Internal Power Supply:
Available Power Output for Transmitters

25 V dc ± 1 V dc @ 80 mA maximum, short circuit protected.

Output Ripple

200 mV p-p maximum

Analog Input (ANI0, ANI1) Signals (all analog in-puts are referenced to signal common)

Quantity

4 (ANI0, ANI1)

Signal Range

0 -5 V dc or 1 -5 V dc (0 -20 mA and 4 -20 mA dc respectively).

NOTE: The rear terminal board has the appropriate resistors for

ANI0 and ANI1.

Input Impedance

1 megohm minimum for voltage inputs; value of ranging resistor for
current signals.

Measurement Accuracy

± 0.1% of span

Contact Input CCI0 Signal (referenced to power common)

Quantity 1

(CCI0)

Type discrete

input

Permitted Contact Resistance

100 ohm maximum

Open/Close Contact Duration

for open recognition: 0.05 seconds minimum
for closed recognition: 0.05 seconds minimum

Contact Recognition Level Closed

1 V dc maximum

Contact Recognition Level Open

4 V dc to 24 V dc

Analog Output (ANO0) Signal (referenced to power common)

Quantity

1 (ANO0)

Signal Range

0 -20 mA dc (4 -20 mA dc typically)

Load Range

0 - 750 ohms

Accuracy

± 0.2% of span

Switch Output (CCO0) Signal (referenced to power common)

Quantity

1 (CCO0)

Type

solid state switch output

Configuration

solid state equivalent of a single pole single throw, normally open or
normally closed contacts referenced to common.

Voltage

30 V dc maximum

Current

50 mA dc maximum

Datalink Communication

RS485, four wire, asynchronous; baud rates 300 to 28,800

Sampling and Update Attributes

Program Scan Rate

0.05 seconds

Analog Input Signal Sampling Rate

0.05 seconds

Contact Input Signal Sampling Rate

0.05 seconds

Display Update

0.10 seconds

Output Signal Update

0.05 seconds

Control Ranges

Proportional Band

2 - 1000% and OFF

Integral

0.02 -200 minutes/repeat or Manual Reset from 0-100%

Derivative

0.01 - 8 minutes and OFF


2