3 easy-tune parameters, Easy-tune, Arameters – Micromod Micro-DCI: 53SL5100B Single Loop Controller User Manual
Page 82: Table 11-1. easy-tune parameters
53SL5100B Single-Loop Controller
INSTRUCTION MANUAL
11.3 EASY-TUNE Parameters
All pertinent input parameters to the EASY-TUNE algorithm are obtained from Controller Module Mode 0,
which must first be configured. The parameters that must be configured before initiating the EASY-TUNE
sequence (B008 = 1) are items 1, 3, 5 through 10, in Table 11-1.
Table 11-1. EASY-TUNE Parameters
Item
Datapoints
Description
Default
1
L520
C385
C386
C387
C388
C389
C390
Enable Tuning Parameter Limits
0 - no limits checked, 1 - limits below apply
lowest % PB
highest % PB
lowest T
R
(minutes)
highest T
R
(minutes)
lowest T
D
(minutes)
highest TD (minutes)
1
2
500
0
30
0
10
2
L521
Abort EASY-TUNE Switch 0 - no effect, 1 - EASY-TUNE is aborted
0
3
L522
Automatic Tuning Parameter 1 - upon successful completion of the
EASY-TUNE sequence, new tuning parameters will be entered. 0 - new
tuning parameters will not be entered but available for review.
0
4
B008
Enable EASY-TUNE
0
5
B385
Control Module Selector (leave at 0)
0
6
B386
PID Control Mode 1 - P, 2 - PI, 3 - PID, 4 - PD, 5 -I
0
7
C378
Excursion Limit for Preliminary Step Disturbance (%) The step size
chosen for C381 will cause a PV change which depends on the
process gain as well as C381 itself. C378 should be set to
approximately 1/4 of that expected change. (See C381 below.)
2
8
C379
Limiting Settling Time (seconds) Set to maximum time allowed during
B387 = 1 or 2. (See Table 11-2 and Figure 11-1.)
0
9
C380
Maximum Allowable Excursion of PV in EASY-TUNE (%) Setting C380
will prevent excessive change in PV.
0
10
C381
Step Size Change in Controller Output (± %) Set large enough to cause
significant but allowable PV changes. (See C378 above.)
0
11
C382
C383
C384
Modifiers to Tuning Criteria (see Section 11.5.)
T
P
Time Constant modifier
K
P
Process Gain modifier
W
P
Dead-Time modifier
12
C391
C392
C393
C394
C395
C396
EASY-TUNE Results (display only):
T
P
Time Constant (seconds)
K
P
Process Gain
W
P
Dead-Time (seconds)
% PB
T
R
(minutes)
T
D
(minutes)
0
0
0
0
0
0
76