11.3 EASY-TUNE Parameters

All pertinent input parameters to the EASY-TUNE algorithm are obtained from Controller Module Mode 0,
which must first be configured. The parameters that must be configured before initiating the EASY-TUNE
sequence (B008 = 1) are items 1, 3, 5 through 10, in Table 11-1.

Table 11-1. EASY-TUNE Parameters

Item

Datapoints

Description

Default

1

L520

C385
C386
C387
C388
C389
C390

Enable Tuning Parameter Limits
0 - no limits checked, 1 - limits below apply
lowest % PB
highest % PB
lowest T

R

(minutes)

highest T

R

(minutes)

lowest T

D

(minutes)

highest TD (minutes)

1

2

500

0

30

0

10

2

L521

Abort EASY-TUNE Switch 0 - no effect, 1 - EASY-TUNE is aborted

0

3

L522

Automatic Tuning Parameter 1 - upon successful completion of the
EASY-TUNE sequence, new tuning parameters will be entered. 0 - new
tuning parameters will not be entered but available for review.

0

4

B008

Enable EASY-TUNE

0

5

B385

Control Module Selector (leave at 0)

0

6

B386

PID Control Mode 1 - P, 2 - PI, 3 - PID, 4 - PD, 5 -I

0

7

C378

Excursion Limit for Preliminary Step Disturbance (%) The step size
chosen for C381 will cause a PV change which depends on the
process gain as well as C381 itself. C378 should be set to
approximately 1/4 of that expected change. (See C381 below.)

2

8

C379

Limiting Settling Time (seconds) Set to maximum time allowed during
B387 = 1 or 2. (See Table 11-2 and Figure 11-1.)

0

9

C380

Maximum Allowable Excursion of PV in EASY-TUNE (%) Setting C380
will prevent excessive change in PV.

0

10

C381

Step Size Change in Controller Output (± %) Set large enough to cause
significant but allowable PV changes. (See C378 above.)

0

11

C382
C383
C384

Modifiers to Tuning Criteria (see Section 11.5.)
T

P

Time Constant modifier

K

P

Process Gain modifier

W

P

Dead-Time modifier

12

C391
C392
C393
C394
C395
C396

EASY-TUNE Results (display only):
T

P

Time Constant (seconds)

K

P

Process Gain

W

P

Dead-Time (seconds)

% PB
T

R

(minutes)

T

D

(minutes)

0
0
0
0
0
0

76