Table 4-5. analog output (ano) module, Table 4-6. contact input module (cci) – Micromod Micro-DCI: 53SL5100B Single Loop Controller User Manual
Page 36
53SL5100B Single-Loop Controller
INSTRUCTION MANUAL
Figure 4-1. ANI0-3
Figure 4-2. ANO0
NOTE: These figures are graphical representations of the signal conditioning that occurs on the
instrument main board. They are provided for reference purposes only.
Table 4-5. Analog Output (ANO) Module
Purpose: The primary purpose of this module is to set the 0 - 20 mA output signal relative to the
displayed percent and to select the analog input signal (ANI0-3) that is to be routed to the analog
output (ANO0).
Title
Symbol
ANO0
Datapoint
Default Attribute
Analog Output
(Display Only)
ANO0
C000
0
The value in this datapoint represents the
percent of output to be generated by hardware
(e.g., 100% output = 20 mA).
0 -20 mA
Output
OZBASE0
L472
0
When a 0, the percentage output generates a 4
-20 mA signal. When set to 1 , the percentage
output generates a 0 -20 mA signal.
Calibrate Zero
COZ0
B267
Calibrate
Span
COS0
C300
These parameters are factory set and should
not need adjustment under normal operation.
See Section 5.3 for adjustment.
Tag Name
AOTAG0
A244
ANO0
The assignable 10 character name for ANO0.
Table 4-6. Contact Input Module (CCI)
Purpose: This module allows the action of the CCI to be reversed (normally a closed contact = 1, but can be
changed to = 0).
Title
Symbol
Datapoint
Default
Attribute
Contact
Input
(Display
Only)
CCI0 L000
0
When open, a 4 -24 V dc input signal = 0 when IINV = 0.
When open, a 4 -24 V dc input signal = 1 when IINV = 1.
When closed, a < 1 V dc input signal = 1 when IINV = 0.
When closed, a < 1 V dc input signal = 0 when IINV = 1.
Contact
Input
Invert
IINV0
L264
0 0
As shown above, it reverses the action of the CCI datapoint.
Tag
Name
CITAG
A262
CCI0
It is an assignable 10 character name for the contact control input.
30