beautypg.com

Table 4-5. analog output (ano) module, Table 4-6. contact input module (cci) – Micromod Micro-DCI: 53SL5100B Single Loop Controller User Manual

Page 36

background image

53SL5100B Single-Loop Controller

INSTRUCTION MANUAL

Figure 4-1. ANI0-3

Figure 4-2. ANO0


NOTE: These figures are graphical representations of the signal conditioning that occurs on the

instrument main board. They are provided for reference purposes only.

Table 4-5. Analog Output (ANO) Module

Purpose: The primary purpose of this module is to set the 0 - 20 mA output signal relative to the
displayed percent and to select the analog input signal (ANI0-3) that is to be routed to the analog
output (ANO0).
Title

Symbol

ANO0

Datapoint

Default Attribute

Analog Output
(Display Only)

ANO0

C000

0

The value in this datapoint represents the
percent of output to be generated by hardware
(e.g., 100% output = 20 mA).

0 -20 mA
Output

OZBASE0

L472

0

When a 0, the percentage output generates a 4
-20 mA signal. When set to 1 , the percentage
output generates a 0 -20 mA signal.

Calibrate Zero

COZ0

B267

Calibrate
Span

COS0

C300

These parameters are factory set and should
not need adjustment
under normal operation.
See Section 5.3 for adjustment.

Tag Name

AOTAG0

A244

ANO0

The assignable 10 character name for ANO0.


Table 4-6. Contact Input Module (CCI)

Purpose: This module allows the action of the CCI to be reversed (normally a closed contact = 1, but can be
changed to = 0).

Title

Symbol

Datapoint

Default

Attribute

Contact
Input
(Display
Only)

CCI0 L000

0

When open, a 4 -24 V dc input signal = 0 when IINV = 0.
When open, a 4 -24 V dc input signal = 1 when IINV = 1.
When closed, a < 1 V dc input signal = 1 when IINV = 0.
When closed, a < 1 V dc input signal = 0 when IINV = 1.

Contact
Input
Invert

IINV0

L264

0 0

As shown above, it reverses the action of the CCI datapoint.

Tag
Name

CITAG

A262

CCI0

It is an assignable 10 character name for the contact control input.

30