Table 4-11. System Module

Purpose: This module is used to set the instrument tag name and the display brightness.

Title

Symbol

System

Module

Datapoint

Default

Attribute

Function Index

FIX

B00

0

The operational algorithm of the unit is selected
by the value of this parameter:
0 = Suspend mode. No control algorithm
execution. The logo is displayed.
1 = CS1, Single Loop PID Controller operation
2 = CS2, Analog Backup Controller operation.
3 = CS3, Ratio Controller operation.
4 = CS4, Automatic/Manual Station operation.
97 = Display Test. The entire display alternately
flashes on and off. When off, a border around
the display perimeter remains lit.
98 = Defaults database then sets FIX to 0.

Display
Brightness
Index

BRIGHT B012

4

This parameter controls the display screen
intensity. A value of 0 is the brightest and a
value of 7 is the dimmest intensity. Normal
viewing setting is 4.

EASY-TUNE
Enable

ETE B08

0

When set to a 1, the EASY-TUNE algorithm is
implemented. This parameter is left at 0 for
normal instrument operation. (See Section 11 for

EASY-TUNE.)

Unit Tag Name

TAG

A08

SL5100

An assignable 10 character name for the system
module (SL5100).

36