Table 4-8. Control Module

Purpose: The primary purpose of this module is to set the instrument’s responsiveness, Alarm Limits 1 &
2, Alarm Dead Band, and the range limits (e.g., 0 - 100, -20 - 80, etc.).

Note:



= applicable to the Control Strategy (CS) as shown in column three.

Title

Symbol

CS

 

1 | 2 | 3 | 4

CON-0

Datapoint

Default Attribute

Control Alarm
Mode

AIX

B335 1

This parameter defines the Alarm Active (PA1
& PA2) interpretation of the two Alarm Limits
(PL1 & PL2). It is entered into the datapoint as
an index value (0-6 ) as follows:
0 PA1n: high when PV> PL1

PA2n: low when PV< PL2

1 None
2 PA1n: high when PV> PL1

PA2n: not affected

3 PA1n: not affected

PA2n: low when PV< PL1

4 PA1n: high when PV> PL1

PA2n: hi-hi when PV> PL2

5 PA1n: low when PV< PL1

PA2n: lo-lo when PV< PL2

6 PA1: Hi-Dev when Dev > PL1

PA2: Lo-Dev when Dev < PL2

Alarm Examples:

B335 PV PL1

(C103)

PL2

(C104)

Alarm

Setpoint Notes

0

>60

60

HIGH

Alarm Llimit 1 is set for 60: PV > 60 = HIGH alarm

0

<40

40

LOW

Alarm Limit 2 is set for 40: PV < 40 = LOW alarm

2

>60

60

HIGH

Alarm Limit 1 is set for 60: PV > 60 = HIGH alarm

2

<40

40

N/A

Alarm Limit 2 is set for 40: PV < 40 = no alarm

3

>60

60

N/A

Alarm Limit 1 is set for 60: PV > 60 = no alarm

3

<40

40

LOW

Low Alarm Limit 2 is set for 40: PV < 40 = LOW alarm

4

>60

60

HIGH

Alarm Limit 1 is set for 60: PV > 60 = HIGH alarm

4

<70

70

HI- HI

Alarm Limit 2 is set for 70: PV > 70 = HI-HI alarm

5

>40

40

LOW

Alarm Limit 1 is set for 40: PV < 40 = LOW alarm

5

<30

30

LO-LO

Alarm Limit 2 is set for 30: PV < 30 = LO-LO alarm

6 >50 10

HI-

DEV

40

Alarm Limit 1 is set for 40: PV < 40 = HI-DEV alarm

6 <30

-10

LO-

DEV

40

Alarm Limit 2 is set for 30: PV < 30 = LO-DEV alarm