Table 4-8. control module – Micromod Micro-DCI: 53SL5100B Single Loop Controller User Manual
Page 38
53SL5100B Single-Loop Controller
INSTRUCTION MANUAL
Table 4-8. Control Module
Purpose: The primary purpose of this module is to set the instrument’s responsiveness, Alarm Limits 1 &
2, Alarm Dead Band, and the range limits (e.g., 0 - 100, -20 - 80, etc.).
Note:
■
= applicable to the Control Strategy (CS) as shown in column three.
Title
Symbol
CS
■
1 | 2 | 3 | 4
CON-0
Datapoint
Default Attribute
Control Alarm
Mode
AIX
■
B335 1
This parameter defines the Alarm Active (PA1
& PA2) interpretation of the two Alarm Limits
(PL1 & PL2). It is entered into the datapoint as
an index value (0-6 ) as follows:
0 PA1n: high when PV> PL1
PA2n: low when PV< PL2
1 None
2 PA1n: high when PV> PL1
PA2n: not affected
3 PA1n: not affected
PA2n: low when PV< PL1
4 PA1n: high when PV> PL1
PA2n: hi-hi when PV> PL2
5 PA1n: low when PV< PL1
PA2n: lo-lo when PV< PL2
6 PA1: Hi-Dev when Dev > PL1
PA2: Lo-Dev when Dev < PL2
Alarm Examples:
B335 PV PL1
(C103)
PL2
(C104)
Alarm
Setpoint Notes
0
>60
60
HIGH
Alarm Llimit 1 is set for 60: PV > 60 = HIGH alarm
0
<40
40
LOW
Alarm Limit 2 is set for 40: PV < 40 = LOW alarm
2
>60
60
HIGH
Alarm Limit 1 is set for 60: PV > 60 = HIGH alarm
2
<40
40
N/A
Alarm Limit 2 is set for 40: PV < 40 = no alarm
3
>60
60
N/A
Alarm Limit 1 is set for 60: PV > 60 = no alarm
3
<40
40
LOW
Low Alarm Limit 2 is set for 40: PV < 40 = LOW alarm
4
>60
60
HIGH
Alarm Limit 1 is set for 60: PV > 60 = HIGH alarm
4
<70
70
HI- HI
Alarm Limit 2 is set for 70: PV > 70 = HI-HI alarm
5
>40
40
LOW
Alarm Limit 1 is set for 40: PV < 40 = LOW alarm
5
<30
30
LO-LO
Alarm Limit 2 is set for 30: PV < 30 = LO-LO alarm
6 >50 10
HI-
DEV
40
Alarm Limit 1 is set for 40: PV < 40 = HI-DEV alarm
6 <30
-10
LO-
DEV
40
Alarm Limit 2 is set for 30: PV < 30 = LO-DEV alarm
32