Table C-2. Database

Title

Symbol

Datapoint

Default

Attribute

Control Tag Name

CTAG

A000

CON-0

Assignable 10 character name that appears with the
control strategy (CS1-4) displays.

Engineering Units

CEU

A001

PERCENT

The default is

PERCENT, but is assignable as units of

measure the Process Variable represents.

System Module Tag
Name

TAG

A008

SL5100

Assignable 10 character name for the system
module.

Parameter Title

PTAG

A014

CON-0

TUNE

Assignable 10 character name for the parameter
display.

Parameter Point 1
Name

PNA

A015

PROP.

BAND

Assignable 10 character name for the Point 1
Designator of the parameter display.

Parameter Point 2
Name

PNB

A016

RESET

Assignable 10 character name for the Point 2
Designator of the parameter display.

Parameter Point 3
Name

PNC

A017

RATE

Assignable 10 character name for the Point 3
Designator of the parameter display.

ANI0 Tag Name

AITAG

A224

ANI0

Assignable 10 character name for analog input 0.

ANI1 Tag Name

AITAG

A225

ANI1

Assignable 10 character name for analog input 1.

ANO0 Tag Name

AOTAG

A244

ANO0

Assignable 10 character name for analog output 0.

CCI Tag Name

CITAG

A262

CCI0

Assignable 10 character name for the contact
control input.

CCO Tag Name

COTAG

A280

CCO0

Assignable 10 character name for the contact
control output.

ANI0 Engineering
Units

AIEU

A298

PERCENT

Assignable for units of meature ANI0 represents
(e.g., GPM for gallons/minute).

ANI1 Engineering
Units

AIEU

A299

PERCENT

Assignable for units of meature ANI1 represents
(e.g., GPM for gallons/minute).

Function
Index

FIX

B000

0

The operational algorithm of the unit is selected by
the
value of this parameter:
0 = Suspend Mode; no control algorithm execution.
The logo is displayed.
1 = CS1, Single Loop PID Controller operation.
2 = CS2, Analog Backup Controller operation.
3 = CS3, Ration Controller operation.
4 = CS4, Automatic/Manual Station operation.
97 = Display Test. The entire display alternately
flashes on and off. When off, a border around the
display perimeter remains lit.
98 = Default Database. Defaults the database, then
sets FIX 0 for suspend mode, which displays the
logo.

Datalink Instrument
Address

IA

B001

0

It identifies the address of this instrument on the
Datalink network. Each unit connected to the
Datalink network must have its own unique address.
Valid addresses are from 0 to 31.

Datalink Baud Rate

BR

B002

253

This datapoint value designates the baud rate (data
transfer rate) of the Datalink network. The baud rate
must be the same for all of the instruments
connected to the same Datalink network. Datapoint
values and their corresponding baud rates are as
follows: