Table c-2. database – Micromod Micro-DCI: 53SL5100B Single Loop Controller User Manual
Page 108
53SL5100B Single-Loop Controller
INSTRUCTION MANUAL
Table C-2. Database
Title
Symbol
Datapoint
Default
Attribute
Control Tag Name
CTAG
A000
CON-0
Assignable 10 character name that appears with the
control strategy (CS1-4) displays.
Engineering Units
CEU
A001
PERCENT
The default is
PERCENT, but is assignable as units of
measure the Process Variable represents.
System Module Tag
Name
TAG
A008
SL5100
Assignable 10 character name for the system
module.
Parameter Title
PTAG
A014
CON-0
TUNE
Assignable 10 character name for the parameter
display.
Parameter Point 1
Name
PNA
A015
PROP.
BAND
Assignable 10 character name for the Point 1
Designator of the parameter display.
Parameter Point 2
Name
PNB
A016
RESET
Assignable 10 character name for the Point 2
Designator of the parameter display.
Parameter Point 3
Name
PNC
A017
RATE
Assignable 10 character name for the Point 3
Designator of the parameter display.
ANI0 Tag Name
AITAG
A224
ANI0
Assignable 10 character name for analog input 0.
ANI1 Tag Name
AITAG
A225
ANI1
Assignable 10 character name for analog input 1.
ANO0 Tag Name
AOTAG
A244
ANO0
Assignable 10 character name for analog output 0.
CCI Tag Name
CITAG
A262
CCI0
Assignable 10 character name for the contact
control input.
CCO Tag Name
COTAG
A280
CCO0
Assignable 10 character name for the contact
control output.
ANI0 Engineering
Units
AIEU
A298
PERCENT
Assignable for units of meature ANI0 represents
(e.g., GPM for gallons/minute).
ANI1 Engineering
Units
AIEU
A299
PERCENT
Assignable for units of meature ANI1 represents
(e.g., GPM for gallons/minute).
Function
Index
FIX
B000
0
The operational algorithm of the unit is selected by
the
value of this parameter:
0 = Suspend Mode; no control algorithm execution.
The logo is displayed.
1 = CS1, Single Loop PID Controller operation.
2 = CS2, Analog Backup Controller operation.
3 = CS3, Ration Controller operation.
4 = CS4, Automatic/Manual Station operation.
97 = Display Test. The entire display alternately
flashes on and off. When off, a border around the
display perimeter remains lit.
98 = Default Database. Defaults the database, then
sets FIX 0 for suspend mode, which displays the
logo.
Datalink Instrument
Address
IA
B001
0
It identifies the address of this instrument on the
Datalink network. Each unit connected to the
Datalink network must have its own unique address.
Valid addresses are from 0 to 31.
Datalink Baud Rate
BR
B002
253
This datapoint value designates the baud rate (data
transfer rate) of the Datalink network. The baud rate
must be the same for all of the instruments
connected to the same Datalink network. Datapoint
values and their corresponding baud rates are as
follows:
102