8.1

SHOW DATA

This menu item will start the data list scrolling on the LCD display. The order of display for up to 16 items
can be designated in the “Setup data display?” menu. Each item can be displayed more than once in the
scan list. Each item will be displayed for approximately two seconds. If an item requires longer display
time, it may be selected for consecutive display points.

The parameters available for display selection (from a total of 19) are dependent upon the Computation
and Hardware setup. The system automatically determines the data available for display based on the
programmed parameters.

DISPLAY DATA DESCRIPTIONS:
1.

Time and Date

Current time and date

2.

Flow Rate

Filtered & Compensated with engineering units

3.

Mass Flow

Filtered & Compensated with engineering units

4.

Heat Flow

Filtered & Compensated with engineering units

5.

Totalizer

Compensated accumulated flow with engineering units

6.

Totalizer

(Mass) Compensated accumulated flow

7.

Heat Totalizer

Compensated accumulated heat flow

8.

Temperature

Filtered & Scaled temperature in degrees

9.

Pressure

Filtered & Scaled pressure in units of measurement

10.

Uncompensated Flow

Filtered but not compensated with engineering units

11.

Raw Flow (Channel 3)

Analog value of flow input

12.

Raw Pressure (Channel 2) Raw analog value of pressure input

13.

Raw Temperature (Channel 1)

Raw analog value of temperature input

14.

Raw RTD Input 1

Raw analog value of RTD input in mA

15.

RTD Ohms (Channel 1)

Resistance of RTD

16.

Analog Output

Output value in mA

17.

Specific Volume

Current specific volume from Steam Tables

18.

Specific Heat

Current specific heat from Steam Tables

19.

Flow Frequency

Raw input pulse frequency


8.1.1

DISPLAY DATA SETUP

Running...
Show Data?


Running...
Go to Standby?


Running...
Setup data display?


Select item #1
Time & Date? Press to advance the list of data available for display

Press to backup the list of data available for display

Press to select the data for display. The item # will increment as each selection is
made

Continue to advance or backup the list and select desired data for display

NOTE: Up to 16 display items may be selected. Pressing the button exits the routine and returns to “Show Data?”

when the desired number of display items is entered. If 16 items are entered, the unit exits the routine and
returns to “Show Data?” upon entering item 16.
(DISREGARD IF RS-232 OPTION IS NOT INSTALLED IN UNIT)

A

A

ENT

B

ENT

A

C