Liquid Controls SP3000 User Manual

Page 11

background image

11

2.2

CONNECTING INPUTS AND OUTPUTS

Make sure all power is disconnected before making any electrical connections. All connections are
completed at the rear terminal strips as indicated in the external wiring diagram. If cables are in areas with
heavy electrical fields, shielding will be required for noise immunity. One end of the shielding should be
connected to earth ground. Figures 2-2 though 2-9 show the input, output and power wiring locations for
the 32 point terminal block on the back of the instrument.

PIN

RTD

VOLTAGE IN

CURRENT IN

FUNCTION

1
2
3
4
5
6

RTD EXCITATION +
RTD SENSE +
RTD SENSE –
RTD EXCITATION –
GROUND (SHIELD)
----------------------------

-------------------------
-------------------------
-------------------------
-------------------------
V IN – (GND)
V IN +

----------------------
----------------------
----------------------
I IN +
I IN – (GND)
----------------------



CHANNEL 1
TEMPERATURE

7
8
9

10
11
12

RTD EXCITATION +
RTD SENSE +
RTD SENSE –
RTD EXCITATION –
GROUND (SHIELD)
----------------------------



-------------------------
-------------------------
V IN – (GND)
V IN +



----------------------
I IN +
I IN – (GND)
----------------------



CHANNEL 2
PRESSURE OR
AUX TEMP

13
14
15

----------------------------
GROUND (SHIELD)
----------------------------

-------------------------
V IN – (GND)
V IN +

I IN +
I IN – (GND)
----------------------

CHANNEL 3
FLOW
ANALOG INPUT

16
17
18

EXCITATION VOLTAGE (5.6K

Ω PULLUP TO 5 VDC)

PULSE INPUT (3-30 VOLTS)
GROUND (SHIELD)

CHANNEL 3
FLOW
ANALOG INPUT

19

ANALOG OUTPUT (SINK)

ANALOG OUT 4-20mA

20
21

PULSE OUTPUT
GROUND (SHIELD)

5 V SCALED
PULSE OUTPUT

22
23
24

N.O.
N.C.
COMMON


ALARM RELAY

25
26
27

N.O.
N.C.
COMMON


FLOW ALARM
RELAY

28
29

115/230 VAC 50/60 HZ
115/230 VAC 50/60 HZ

POWER (AC)

30
31

+24 VOLTS ISOLATED Output available
24 VOLTS RTN on AC Powered Units

+24 VDC IN Power input for
-- DC (GND) DC Powered Units

32

CHASSIS GROUND


Figure 2-2

Terminal Designation Label