Use Table 4 to determine high voltage wire size requirements. The distance shown in the chart is
measured in feet from the operator to the power source. If power wiring is greater than the maximum
distance shown, it is recommended that a service feeder be installed. When large gauge wire is
used, a separate junction box must be installed for the operator connection. The wire table is based
on stranded copper wire. Wire run calculations are based on a 110 VAC power source with a 3%
voltage drop on the power line, plus an additional 10% reduction in distance to allow for other losses
in the system.

2.1.1 SINGLE

OPERATOR

• Route incoming high voltage power

through conduit and into the operator
as shown in Figure 23.

• Be sure wiring is installed in

accordance with local codes. Be sure
to color code all wiring.

• Connect BLACK power wire to the

HOT terminal as shown.

• Connect WHITE neutral wire to NEUT

terminal as shown.

• Connect GREEN ground wire to

ground lug.

• It is recommended that a surge

suppresser be installed on the high
voltage power lines to help protect the
operator and circuit board from surges
and power fluctuations.

2.1 HIGH

VOLTAGE

CONNECTIONS

WIRE SIZE / DISTANCE IN FEET

MODEL AMPS

12 AWG

10 AWG

8 AWG

6 AWG

6050

SINGLE

4.3 215 345 575 890

6050 M / S

8.6

105

170

285

430

6100

SINGLE

5.4 170 275 460 685

6100 M / S

10.8

85

135

230

340

Table 4

CONDUIT

POWER SWIT

CH

HIGH VOLTAGE

TERMINAL STRIP

117 V

A

C

HOT

NEUT

GROUND

LUG

Figure 23