Jog has the least operating priority. Jog ramps to the Jog Setpoint (CP-05), using the
Acceleration Time (CP-16). When Jog is terminated, the MLP–Drive brings the drive
output to an immediate Zero. Unlike the other inputs, Jog is not latched and must be
sustained to remain active.
To activate Jog:
• Short the F–Stop and R–Stop inputs to common.
• Open the Run input.
• Short the Jog input to common. (Jog must be sustained to remain active).
R-STOP
F-STOP
RUN
JOG
R-STOP
F-STOP
COMMON
JOG
RUN
Maintain Closed
4
5
6
7
8
J5