Parameter send, Character 1 - stx, Characters 2, 3 - device – CONTREX MLP-Drive User Manual
Page 115: Character 4 - message type

3 - 77
Parameter Send
Use the Parameter Send to change any of the MLP-Drive's Control Parameters.
Table 3-51 Parameter Send - Host Transmission
Character #
1
2
3
4
5
6
7
8
9
10
11
12
DEV # DEV # MSG
PAR # PAR #
DATA DATA
DATA
DATA
DATA
DESC
STX
10s
1s
TYPE
10s
1s
1000s 100s
10s
1s
FORM
ETX
ASCII
STX
0-9
0-9
3
0-9
0-9
0-9
0-9
0-9
0-9
0-8
ETX
The following is a description of the Parameter Send-Host Transmission Characters.
Character 1 - STX:
This is the first character in the character string. None of the other characters will
be recognized without this character prefix. Always use the ASCII “STX” character;
it enables the MLP-Drive's receive buffer.
Characters 2, 3 - Device #:
These characters are the access address of the MLP-Drive. This number identifies
individual MLP-Drives on a mutltidrop system. The MLP-Drive will accept data only
if this number matches the MLP-Drive's address (CP-70), with the exception of a
“00” address. The “00” address is universally accepted by all of the MLP-Drives
that are on the RS485 Serial Communications Interface.
Character 4 - Message Type:
This character should always be “3”.