Master Mode Example
The following example demonstrates how scaling and setpoint Control Parameters are
entered for a typical Master mode of operation:
A pump delivers 15 gallons/minute when the motor runs at a maximum
RPM of 1725. The motor shaft is equipped with a 30 tooth Ring kit.
The Master Engineering Units are gallons per minute. Master Setpoint
1 will be setup to pump 10 gallons per minute when it is the active
setpoint. Master Setpoint 2 will be setup to pump 5 gallons per minute
when it is the active setpoint.
Table 3-7 shows the scaling Control Parameters that would be entered in the
MLP–Drive for this example.
Table 3-7 Master Mode Control Parameters Example
CP
Parameter Name
Parameter Value
CP-34
Max RPM Feedback
1725
CP-31
PPR Feedback
30
CP-20
Master Engineering Units
15.0
CP-01
Master Setpoint 1
10.0
CP-02
Master Setpoint 2
5.0
After the Scaling and the Master Setpoints for your system have been entered, you can
enter the Acceleration/Deceleration Control Parameters for the Master mode. The
Acceleration/Deceleration Control Parameters are identical for both the Master and the
Follower modes of operations. Acceleration/Deceleration is discussed in
Operation:
Control Parameters, Acceleration/Deceleration.