CONTREX MLP-Drive User Manual
Page 55

3 - 17
Table 3-12 Entering Master Scaling Analog Setpoint Parameters
CP
Parameter Name
Parameter Value
CP-84
Analog Input Allocation
CP-20
Master Engineering Units
CP-34
Max RPM Feedback
CP-31
PPR Feedback
Setting CP-84 to a value of "4" or "5"
allocates the analog input to be used
as Master Setpoint 1 or Master
Setpoint 2, respectively.
Enter the Master Engineering Unit
value for an analog setpoint level of
10.0 volts and feedback RPM of CP-34.
Enter the maximum operating RPMs
measured at the feedback sensor shaft.
Enter the resolution of the feedback
sensor.