Specifications (continued), Dc ok relay contact, Application of dc ok active signal – GF Signet 7310 Switching Power Supplies User Manual
Page 3

www.gfsignet.com
Front View
Side View
7310-1024
7310-2024
7310-4024
7310-6024
7310-7024
Environment
Working Temperature
-20 ~ +70 °C (Refer to output load Derating Curve)
10 ~ +60 °C
(Refer to output
load Derating
Curve)
Working Humidity
20 ~ 90% RH non-condensing
Storage Temp., Humidity
-40 ~ +85 °C, 10 ~ 95% RH
Temp. Coefficient
±0.03%/ °C (0~50 °C)
Vibration
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes;
Mounting: Compliance to IEC60068-2-6
Safety and EMC (Note 4)
Safety Standards
UL508, TUV EN60950-1
approved,
NEC class 2 / LPS
compliant
UL508, UL60950-1,
TUV EN60950-1 approved
UL508, TUV
EN60950-1
approved
Withstand Voltage
I/P-O/P:3KVAC
I/P-FG:1.5KVAC
O/P-FG:0.5KVAC
I/P-O/P:3KVAC
I/P-FG:2KVAC
O/P-FG:0.5KVAC
I/P-O/P:3KVAC
I/P-FG:1.5KVAC
O/P-FG:0.5KVAC
Isolation Resistance
I/P-O/P, I/P-FG,
O/P-FG:100M Ω
500VDC / 25 °C /
70% RH
I/P-O/P, I/P-FG,
O/P-FG:100MΩ
/500VDC
I/P-O/P, I/P-FG,
O/P-FG:>100MΩ /
500VDC / 25 °C /
70% RH
I/P-O/P, I/P-FG,
O/P-FG:>100MΩ /
500VDC / 25 °C /
70% RH
I/P-O/P, I/P-FG,
O/P-FG:>100Ω /
500VDC / 25 °C /
70% RH
EMC Emission
Compliance to EN55011, EN55022 (CISPR22), EN61204-3 Class B, EN61000-3-2,-3
EMC Immunity
Compliance to EN61000-4-2, 3, 4, 5, 6, 8, 11, EN55024,EN61000-6-1,EN61204-3, light industry level,
criteria A
Others
MTBF
584K hrs min
MIL-HDBK-217F
(25 °C)
236.9K hrs min
MIL-HDBK-217F
(25 °C)
301.7K hrs min
MIL-HDBK-217F
(25 °C)
299.2K hrs min
MIL-HDBK-217F
(25 °C))
346K hrs min
MIL-HDBK-217F
(25 °C))
Dimension
22.5*90*100mm
(W*H*D)
22.5*90*100mm
(W*H*D)
40*90*100mm (W*H*D)
55*90*100mm
(W*H*D)
Packing
0.17Kg; 72pcs/
13.2Kg/.0.91CUFT
0.19Kg; 72pcs/
14.7Kg /0.91CUFT
0.3Kg; 42pcs/
13.6Kg/0.82CUFT
0.33Kg; 42pcs/
14.8Kg/0.82CUFT
0.42Kg; 30pcs
/13.6Kg/0.82CUFT
Note
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 °C of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.
5. Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
Specifications (continued)
7310-7024
Contact close
PSU turns on/DC okay
Contact open
PSU turns off/DC fail
Contact ratings (max.)
30V/1A resistive load
7310-4024, 7310-6024, 7310-7024
DC OK Relay Contact
DC OK
V-
R
3.9k
5.1V
DC OK
V-
R
4.7k
DC OK
V-
RL
1.2k
Relay
5V Signal
LED
Relay
Application of DC OK Active Signal
7310-1024, 7310-2024
0
-20
0
10
20
30
40
50
60
Ambient Temperature (°C)
Load (%)
20
40
60
80
100
Derating Curve
70
7310-1024, 7310-4024
7310-2024
7310-6024
7310-7024
Output Derating Vs. Input Voltage
50
80
100
120 140
160
180 200 240
Input voltage (VAC) 60 Hz
Load (%)
60
70
80
90
100
264
+
+V +V
09
-V -V
N
L
+V ADJ
55
100
90
5
7.5
7.5
5
5
55