Wiring Tips:
• Do not route sensor cable in conduit containing AC power wiring. Electrical

noise may interfere with the signal.

• Routing cable in grounded metal conduit will help prevent electrical noise and

mechanical damage.

• Seal cable splices tightly to prevent moisture damage.
• The cable length from the 8058 to the 8900/9900 must not exceed the S

3

L

limitations as defi ned in the instruction manuals.

1. Wire the 8058-1 between the 4 to 20 mA loop source and the 8900 S

3

L input terminals as illustrated.

2. In the 8900 menu, assign a channel for this input, and specify the

input parameter.

If the 4 to 20 mA SOURCE is one of the standard 8900 input
parameters (Flow, pH, Conductivity, etc.) select that channel type.

If the 4 to 20 mA SOURCE is not included in the 8900 menu,
select OTHER (4-20) and then set additional labels and
abbreviations per the 8900 instructions.

3. Follow complete instructions in the 8900 manual to set up the

new channel.

1. Wire the 8058-2 between the 4 to 20 mA loop source and the 8900 S

3

L input terminals as illustrated.

2. In the 8900 menu, assign a channel for this input, and specify

the input parameter.

If the 4 to 20 mA SOURCE is one of the standard 8900 input
parameters (Flow, pH, Conductivity, etc.) select that channel
type.

If the 4 to 20 mA SOURCE is not included in the 8900 menu,
select OTHER (4-20) and then set additional labels and
abbreviations per the 8900 instructions.

3. Follow complete instructions in the 8900 manual to set up the

new channel.

CAUTION
Loop power must not exceed 35 VDC.

The green DATA LED indicates when
the data output is active.

The red Loop LEDs indicate when one
or both of the 4 to 20 mA loop inputs
are powered.

3 2 1

6 5 4

7 8 9

Loop1

PWR

N/C

S

3

L

DATA

Loop2

PWR

+GF+ SIGNET

Two 4 to 20 mA loop signals can be
connected to the 8058-2.

The S

3

L output terminals carry the input

loop signals.

The 8058-2 accepts two 4 to 20 mA loop input signals and
converts them into two S

3

L serial data signals for input to the

Signet 8900, where each loop is completely independent. The
8058 transmits information to identify the two signals by using the
serial number of the 8058 converter:

1

2

3

4

5

6

7

8

9

10

11

12

13

14

3 2 1

6 5 4

7 8 9

Loop1

PWR

N/C

S L

DATA

3

Loop2

PWR

+GF+ SIGNET

+

+

-

+

-

-

Power

Supply

12-24 VDC

4-20 mA Loop 2

Source

4-20 mA Loop 1

Source

BLACK (5 VDC)

RED (S

3

L)

BLACK

BLACK

RED

WHITE (GROUND)

8900 terminals

8058-2 DIN Rail Mount to Signet 8900 Multi-Parameter Controller

• The manufacture date of the 8058 is included in the serial number label

on the instrument.

• The 8058 converter transmits the serial number onto the S

3

L bus as the

ID for the Loop 1.

• The 8058 transmits a second serial number for Loop 2 by by adding 12

to the month. (6040630.... becomes 6041830....)

Month

mfg

Day
mfg

Year

mfg

Sequential

Disregard

Loop 1: 6 04 06 30 1234

X

X

Loop 2: 6 04 18 30 1234

CAUTION
Loop power must not exceed 35 VDC.