Maintenanceandtroubleshooting

problem

bargraph
state

red leD state

Green leD
state

current or
frequency
output
state

meaning / cause

recommended action

The flow rate
measure-
ments are not
stable

Unstable

OFF

Flashes once
every second

> 4 mA
and
> 0 Hz

The electrodes are dirty.

Clean the electrodes (see chap.
10.3).

The electrodes are not in
contact with the fluid.

Make sure the electrodes are always
in contact with the fluid

Air bubbles appear in the
fluid.

Respect the mounting recommenda-
tions (see chap. 8.2).

Select the "slow" filter (see chap.
9.5).

The flow sensor has not
been immersed for 24 h
before calibration of the
"flow zero" point.

Respect the calibration procedure
(see chap. 9.7).

The flow rate fluctuations
are very important.

Select the "slow" filter (see chap.
9.5).

Upstream-downstream
connection has not been
correctly done.

Respect the mounting recommenda-
tions (see chap.

8.2).

The device
transmits no
current or no
frequency at
all.

shows a
value

OFF

Flashes once
every second

0 mA and/or
0 Hz

The position of the sink/
source selector is not
correct.

Correctly position the sink/source
selector (see chap. 8.3.1).

The outputs are not cor-
rectly wired.

Check the wiring of the outputs (see
chap. 8.3.1, 8.3.2, 8.3.3).

The sensor
does not
measure a nil
flow rate.

Lit

OFF

Flashes once
every second

> 4 mA and
> 0 Hz

The calibration of the flow
zero point has not been
correctly done.

Calibrate again (see chap. 9.7).

English

Type 8041