beautypg.com

Fig. 42 – Burkert Type 8041 User Manual

Page 46

background image

44

Adjustmentandcommissioning

Release the push button when desired number
of LEDs is on.

to set the units for the low switching threshold.

Briefly press push button

After 2 s, next LED flashes;
1 flash = 1 % of the FS

If low switching threshold set to 24%, LED no. 3
flashes 9 times then stays on;
1 flash = 1 % of the FS

Next LEDS come on one after the other until they
show the factor of ten for the current high switching
threshold;
1 LED ON = 10 % of the FS

A

If high switching threshold set to 82%, LED no. 9
flashes 9 times then stays on;
1 flash = 1 % of the FS

Next LEDS come on one after the other until they
show the factor of ten for the current low switching
threshold;
1 LED ON = 10 % of the FS

Release the push button when desired number of
LEDs is on.

to set the units for the high switching threshold.

Briefly press push button

After 2 s, next LED flashes;
1 flash = 1 % of the FS

Release push button when LED has flashed the desired
number of times

B

C

Fig. 42: Setting the relay switching thresholds, part 2

English