beautypg.com

Fig. 15), Fig. 16), Fig. 16 – Burkert Type 8041 User Manual

Page 25

background image

23

INstallation

note

the device is not tight if only one or none of the cable glands
is used
• The device is only tight when the cable glands are either wired or

sealed. To seal a cable gland, do the following:

Loosen the nut of the unused cable gland.

Remove the transparent disk.

Insert the supplied stopper gasket.

Screw the nut of the cable gland.

Loosen the nuts of the cable glands.

Insert each cable through a nut than through a cable gland.

1 2 3 4 5 6

Power cable shield

Earth cable coming from the

housing

Second cable on a version with
a flow sensor holder in stainless
steel

Fig. 15: Earth connection terminal

+

-

18-36 VDC

1

2

2

Power cable shield

Power supply

Fig. 16: Earthing the device

Wire the 4-20 mA current output (see 8.3.1).

Wire the frequency output (see 8.3.2).

Wire the relay output (see 8.3.3).

Put the cover of the housing as described in Fig. 17.

Screw the 4 screws in an alternating pattern.

Fig. 17: Position of the cover of the device

English

Type 8041