INstallation

8.3.1. Wiring the 4-20 mA output

The current output of the 8041 can be connected to a PLC or a
valve, either in sourcing mode or in sinking mode.

Set the selector of the electronic board to the sourcing or the
sinking position (see

Fig. 18 or Fig. 19).

Connect the 4-20 mA output in sourcing mode (see Fig. 18) or
in sinking mode (see Fig. 19).

Earth the device (see Fig. 18

or Fig. 19).

1 2 3 4 5 6

V+ V- PE Pls+Pls-

+

-

+

-

*

18-36 VDC

300 mA

I

4...20

Power supply

4-20 mA input
at external
instrument

Selector to

source

* If direct earthing is not possible, connect a 100 nF / 50 V condensator
between the negative terminal of the voltage supply and the earth.

Fig. 18: Connection of the current output in sourcing mode

1 2 3 4 5 6

4...20 V+ V- PE Pls+Pls-

+

-

+

-

18-36 VDC

300 mA

*

I

4-20 mA input
at external
instrument

Power supply

Selector to sink

* If direct earthing is not possible, connect a 100 nF / 50 V condensator
between the negative terminal of the voltage supply and the earth.

Fig. 19: Connection of the current output in sinking mode

8.3.2. Wiring the frequency output

Connect the frequency output:

- to a PLC in PNP or in NPN mode (see Fig. 20 and Fig. 21) ;

- or to a load such as an electromechanical counter or a relay

(see Fig. 22),

- or to a load such as an electronic counter with its own power

supply (see Fig. 23).