beautypg.com

Burkert Type 8041 User Manual

Page 53

background image

51

Maintenanceandtroubleshooting

problem

bargraph
state

red leD state

Green leD
state

current or
frequency
output
state

meaning / cause

recommended action

The device
does not
respond

OFF

Flashes 5 times
briefly every 2 s

Flashes once
every second

22 mA and
0 Hz

The calibration of the full
scale failed because the
fluid velocity > 10 m/s.

Clear the error by briefly pressing the
push-button.

Check the fluid velocity.

Restart the calibration of the full
scale (see chap. 9.8).

The sensor
does not
work

OFF

OFF

OFF

0 mA
and
0 Hz

The device is not
connected.

Connect the device.

The fuse of the installation
is in a bad condition

Replace the fuse.

The switch of the instal-
lation is set to OFF

Position the installation switch to ON.

-

The power supply has
been wrong connected to
the + and - terminals

Check the wiring (see chap. 8.3.1,
8.3.2, 8.3.3).

Flashes irreg-
ularly or is off

0 mA
and
0 Hz

The power supply is not
stable.

Replace the power supply.

OFF

0 mA
and
0 Hz

The device is out of
service

Return the device to your Bürkert
retailer.

Incorrect flow
measurement.

-

OFF

Flashes once
every second

-

The K factor has not been
correctly calculated.

Recalculate the K factor (see chap.
6.7).

All the
LEDs are
ON

OFF

Flashes once
every second

20 mA and
240 Hz

Measuring range
exceeded by less than
20%.

Select the higher measuring range
(see chap. 9.6)

English

Type 8041