Adjustmentandcommissioning

The wiring of the relay determines the function of the relay:
Normally Open (NO) or Normally Closed (NC).

The following parameters of the relay output can be set:

- the switching way: window or hysteresis (see chap. 9.9.1)

- the value of the low switching threshold, as a percentage of the

full scale (see chap. 9.9.2)

- the value of the high switching threshold, as a percentage of

the full scale (see chap. 9.9.2)

- the time delay before switching: from 0 to 100 seconds (see

chap. 9.9.3).

9.9.1. choosing the switching way of the

relay output

Two switching ways of the relay are available, window or hysteresis.
In window switching, the state of the relay output is changed
whenever one of the thresholds is detected (see Fig. 35 and

Fig.

36).

State of the relay output

deactivated

actived

Low threshold

High threshold

m/s

Fig. 35: Change of state of the relay output in window switching

with a relay wired as NO

State of the relay output

deactivated

actived

Low threshold

High threshold

m/s

Fig. 36: Change of state of the relay output in window switching

with a relay wired as NC

In hysteresis switching (see Fig. 37 and Fig. 38), the state of the
relay output is changed:
• when both the high threshold is detected and the fluid velocity

increases;

• when both the low threshold is detected and the fluid velocity

decreases;

State of the relay output

deactivated

actived

Low threshold

High threshold

m/s

Fig. 37: Change of state of the relay output in hysteresis switching

with a relay wired as NO