beautypg.com

Selecting the frequency of the main supply, Filter selection – Burkert Type 8041 User Manual

Page 34

background image

32

Adjustmentandcommissioning

9.4.

selecting the frequency of the
main supply

Switch 1 is used to select the frequency of the current provided by
the electricity network.

Position switch 1 to ON or OFF depending on the frequency of
the main supply (see Fig. 26, chap. 9.2,

and the following table).

Frequency of the power sup-
plied by the network

Position of switch 1

50 Hz

OFF

60 Hz

ON

9.5.

filter selection

The filter is used to attenuate the fluctuations in the flow indicated by
the bargraph and on the current and frequency outputs. The device
can operate with or without filter.

Position switch 2 (see Fig. 26, chap. 9.2,

and the following

table) to activate or deactivate the filter feature.

Filter

Position of switch 2

disabled

OFF

enabled

ON

When the filter is enabled, switch 3 is used to select the filter level:
slow or fast.
"Slow" filter is used to even out high variations in flow (example: fluid
containing air bubbles), see Fig. 27.
"Fast" filter is used to even out low variations in flow (see Fig. 27).

t (s)

t (s)

t (s)

Actual flow rate

Flow attenuated with fast filter

Flow attenuated with low filter

Fig. 27: Flow filters

Position switch 3 to the filter level selected (see Fig. 26, and the
following table).

English

Type 8041