General data – Burkert Type 8041 User Manual
Page 13
11
Technicaldata
Table 4 : Dimension H in mm of the flowmeter 8041 with a clamp
connection and inserted into an S020 fitting
H
T-fitting
Welding socket
DN32
181
181
DN40
186
186
DN50
191
191
DN65
199
199
DN80
205
205
DN100
211
211
6.4.
General data
Pipe diameter
DN06 to DN400
Type of fitting
S020
Fluid conductivity
> 20 µS/cm
1)
Determined in the following reference conditions: fluid = water, water
and ambiant temperatures = 20 °C, upstream and downstream distances
respected, appropriate pipe dimensions
Fluid temperature
• with holder of the flow
sensor in stainless steel
• with holder of the flow
sensor in PVDF
The fluid temperature may be
restricted by the fluid pressure and
the material of the S020 fitting used
(see
• -15...+150 °C
• 0...+80 °C
Fluid pressure
• with holder of the flow
sensor in stainless steel
• with holder of the flow
sensor in PVDF
The fluid pressure may be restricted
by the fluid temperature, the material
of the S020 fitting used and the DN
of the S020 fitting used (see Fig. 6
and
Fig. 7).
• PN10 with a fitting in plastic,
PN16 with a fitting in metal
• PN10
Flow rate measurement
• Measuring range
• Linearity
• Repeatability
• Accuracy with standard
K factor
• Accuracy with Teach-in
• 0,2 to 10 m/s
1)
• ±0,5%
1)
of the full scale
• ±0,25%
1)
of the measured value
• ±3,5%
1)
of the measured value
• ±0,5%
1)
of the measured value