14

Quickinstallation

7.

QuicK insTAllATion

Contact your Bürkert
agent

Unpack the device.

Order code

correct?

Loosen 4 screws and remove

cover.

yes

No

Select the frequency of the main
supply with switch 1, see chap.

9.4.

Select the filter with switches 2
and 3, see chap. 9.5.

Select the current output type,
see chap. 8.3.1.

The following formulae are used to calculate the K

1

and K

2

factors

needed to convert the current or frequency into a flow rate:

Full scale

K factor K

1

K factor K

2

10 m/s

K

1

= 100

K

fitting

K

2

= 20

3*K

fitting

5 m/s

K

1

= 200

K

fitting

K

2

= 40

3*K

fitting

2 m/s

K

1

= 500

K

fitting

K

2

= 100

3*K

fitting

where K

fitting

= K factor of the S020 fitting used

Example:
If the full scale of the device is set to 5 m/s, the value of the current
output will be:
I = 40 Q + 4
3*K

fitting

with I in mA, K

fitting

in pulse/litre and Q in l/s.

English

Type 8041