Quick installation – Burkert Type 8041 User Manual
Page 16
14
Quickinstallation
7.
QuicK insTAllATion
Contact your Bürkert
agent
→
Unpack the device.
Order code
correct?
→
Loosen 4 screws and remove
cover.
yes
No
→
Select the frequency of the main
supply with switch 1, see chap.
→
Select the filter with switches 2
and 3, see chap. 9.5.
→
Select the current output type,
see chap. 8.3.1.
The following formulae are used to calculate the K
1
and K
2
factors
needed to convert the current or frequency into a flow rate:
Full scale
K factor K
1
K factor K
2
10 m/s
K
1
= 100
K
fitting
K
2
= 20
3*K
fitting
5 m/s
K
1
= 200
K
fitting
K
2
= 40
3*K
fitting
2 m/s
K
1
= 500
K
fitting
K
2
= 100
3*K
fitting
where K
fitting
= K factor of the S020 fitting used
Example:
If the full scale of the device is set to 5 m/s, the value of the current
output will be:
I = 40 Q + 4
3*K
fitting
with I in mA, K
fitting
in pulse/litre and Q in l/s.
English
Type 8041
- Type 1062 (112 pages)
- Type 1050 (4 pages)
- Type 8750 (64 pages)
- Type 8750 (82 pages)
- Type 8681 (40 pages)
- Type 8681 (90 pages)
- Type 8798 (2 pages)
- Type 8791 (4 pages)
- Type 8798 (106 pages)
- Type 8792 (136 pages)
- Type 8792 (252 pages)
- Type 8718 (34 pages)
- Type 8792 (118 pages)
- Type 8791 (15 pages)
- Type 8791 (106 pages)
- Type 8791 (184 pages)
- Type 8791 (28 pages)
- Type 8791 (21 pages)
- Type 8791 (154 pages)
- Type 0911 (84 pages)
- Type 0911 (76 pages)
- Type 0911 (46 pages)
- Type 0911 (64 pages)
- Type 1058 (31 pages)
- Type 1060 (4 pages)
- Type 1066 (112 pages)
- Type 1067 (158 pages)
- Type 1077-2 (33 pages)
- Type 1094 (126 pages)
- Type 1094 (12 pages)
- Type 1094 (41 pages)
- Type 1094 (82 pages)
- Type 1115 (25 pages)
- Type 1150 (99 pages)
- Type 1541 (2 pages)
- Type 5142 (6 pages)
- Type 8619 (40 pages)
- Type 8619 (134 pages)
- Type 8620 (177 pages)
- Type 8622 (4 pages)
- Type 8623 (130 pages)
- Type 8623 (90 pages)
- Type 8625 (118 pages)
- Type 8624 (124 pages)
- Type 8718 (254 pages)