beautypg.com

Electrical connections, K factors – Burkert Type 8041 User Manual

Page 15

background image

13

Technicaldata

Current output

• Type of output
• Accuracy
• Refresh time
• Max. loop impedance

• 4-20 mA, sinking or sourcing wiring
• ± 1% (0,16 mA)
• 100 ms
• 1100 W at 36 V DC, 330 W at

18 V DC

Frequency output

• Frequency
• Duty cycle
• Max current
• Protected against

short-circuits and
polarity reversal

• 0-240 Hz
• 50 % ± 1 %
• 100 mA max.
• yes

Relay output

• Normally open or normally closed,

depending on the wiring

• 3 A, 250 V AC max.

Alarm
• Full scale exceeded
• Error signal

• 22 mA and 256 Hz
• 22 mA and 0 Hz

6.6.

electrical connections

Type of connection

Through two M20x1,5 cable
glands

Cable specifications
• cable type
• Cross section
• Diameter of each cable:

- if only one cable is used

per cable gland

- if two cables are used per

cable gland

• shielded
• 0,5 to 1,5 mm

2

- 6...12 mm

- 4 mm, with the supplied

multi-way seal

6.7.

K factors

The S020 fitting with weld end connections is available
in two versions: a version for the measuring devices with

a G2'' nut and a version for the measuring devices with a

clamp connection.
• Use the K factor of the fitting used.

The device measures the flow velocity (in m/s) of the fluid and converts
it into a current (in mA) and a frequency rating (in Hz).
The current I or the frequency f are proportional to the flow rate Q (l/s),
the proportionality factor is called the "K factor":

f = K

1

*Q

I = K

2

*Q + 4

with K

1

and K

2

in pulse/litre

English

Type 8041