Installing a t fitting – Burkert Type S020 User Manual
Page 32

32
Installationandcommissioning
Type S020
Correct
Correct
Incorrect
Incorrect
Flow direction
Flow
direction
Fig. 9: Additional recommendations on installation
7.2.2. installing a T fitting
Follow	the	recommendations	on	installation	described	in	
chap.	7.2.1.
note
the	seal	on	the	fitting	with	welding	end	connections	may	be	
damaged	during	welding.
Version	for	measuring	devices	with	a	G2''	nut:
•	 Before	welding	the	welding	ends,	remove	the	adapter	from	the	
fitting by unscrewing the 4 screws and remove the seal.
• After welding, correctly put the seal in the groove and the adapter
on	the	fitting,	tighten	the	4	screws,	applying	a	nominal	tightening	
torque	of	2	Nm.
Version	for	measuring	devices	with	a	clamp	connection:
•	 Before	welding	the	welding	ends,	remove	the	seal.
•	 After	welding,	correctly	replace	the	seal	in	the	groove.
→
Install	the	fitting	by	turning	one	of	the	polarising	slots	opposite	
the	flow	direction.
English
