K factors (in pulse/litre) for screw-ons – Burkert Type S020 User Manual
Page 28

28
Technicaldata
Type S020
6.4.8. K factors (in pulse/litre) for screw-ons
When	the	dimensions	of	your	pipe	are	slightly	different	from	dimensions	d	and	s	given	in	the	table,	recalculate	the	K	factor	using	one	
of	the	formulae	in	chap.	6.4.2.
If	the	measuring	device	does	not	automatically	convert	the	K	factor,	use	the	following	conversion	formulae	before	setting	the	para-
meters	of	the	device:
•	 K	factor	in	pulse/US	gallon	=	K	factor	in	pulse/litre	x	3.785
•	 K	factor	in	pulse/UK	gallon	=	K	factor	in	pulse/litre	x	4.546
Table 22: K factors, external diameters and theoretical cross-sections of screw-ons
measuring device inserted
8020, 8024, 8025, 8026
8041, 8045
external diameters and theoretical
cross-sections
material of the pipe
pVc
pp / pe
pVc
pp / pe
d
pVc
[mm]
s
pVc
[mm]
d
pe/pp
[mm]
s
pe/pp
[mm]
dn
100
4,83 (L)
5,29 (L)
33,0 (L)
30,4 (L)
110
8,1
110
10
110
3,45 (L)
-
44,7 (L)
-
125
9,2
125
11,4
125
2,55 (L)
3,10 (L)
63,7 (L)
52,1 (L)
140
10,3
140
12,8
150
1,67 (L)
2,12 (L)
137 (L)
78,8 (L)
160
6,2
160
14,6
180
1,08 (L)
1,37 (L)
197 (L)
116 (L)
200
9,6
200
18,2
200
0,80 (L)
1,07 (L)
290 (L)
147 (L)
225
8,6
225
20,5
250
-
0,63 (L)
-
347 (L)
-
-
280
25,5
300
-
0,42 (L)
-
510 (L)
-
-
315
28,7
350
-
0,30 (L)
-
705 (L)
-
-
355
32,3
400
-
0,23 (L)
-
931 (L)
-
-
400
36,4
(L): long sensor version
English