Start-Up
Type 8792, 8793
16.3.1 Basic settings of the process
controller
→
In the main menu (MAIN) select the P.CONTROL function and
make the basic settings.
EXIT
ENTER
16
M A I N
P.CONTROL
ADD.FUNCTION
P.TUNE
EXIT
EXIT
PID.PARAMETER
SETUP
DBND 0,1 %
PV-INPUT
KP 0,00
PV-SCALE
TN 0,5
SP-INPUT
TV 0,0
SP-SCALE*
X0 0,0 %
P.CO-INIT
FILTER 0
P.CONTROL
ENTER
ENTER
ENTER
EXIT
Main menu
* The SP SCALE function
appears only when the
external preselected set-
point value (external) menu
option is activated under
SP INPUT.
Fig. 26: Operating structure - basic settings of the process controller
P.CONTROL - settings:
PID.PARAMETER Parameter settings of the process controller
DBND 0,1 % Insensitivity area of the PID process controller
KP 0,00 Amplification factor of the process controller
TN 0,5
Reset time
TV 0,0
Hold-back time
X0 0,0 %
Operating point
FILTER 0
Filtering of the process actual value input
SETUP
Setting up the process controller:
PV-INPUT
AIndication of the signal type for process
actual value
PV-SCALE
Scaling the process controller
SP-INPUT
Type of the set-point value default (internal or
external)
SP-SCALE*
Scaling the position controller (for external set-
point value default only)
P.CO-INIT
Enables a smooth switchover between AUTO-
MATIC and MANUAL operating state
Tab. 26: Basic settings of the process controller
Parameters can be set automatically with the aid of the
P.TUNE
function (description see “Operating instructions for Type
8792/8793”).