Electrical Installation
Type 8792, 8793
Connection of a potentiometric position sensor:
Terminal Configuration
On the
device
side
External circuit
Potentiometer 1 1
Potentio-
meter
Center tap 2
2
Center tap
Potentiometer 3 3
Tab. 16: Terminal assignment; potentiometric position sensor
When the operating voltage is applied, the positioner is operating.
→
Now make the required basic settings and actuate the automatic
adjustment of the positioner. The procedure is described in chapter
“16.2 Starting-up Type 8792”
14.7 Terminal assignment for cable
gland - process controller Type
8793
→
First connect the process controller as described in chapter
“14.6 Terminal assignment for cable gland - positioner Type
8792” .
14.7.1 Terminal assignments of the process
actual value input
Input
type*
Terminal Configuration
On the
device side
External
circuit
4 ... 20 mA
- internally
supplied
actual value
1
+24 V Input
transmitter
1
2
3
GND
Trans-
mitter
GND
2
Output from
transmitter
3
Bridge to GND
(Terminal GMD from
operating voltage)
4
not used
GND
GND from operating
voltage
4 ... 20 mA
- externally
supplied
actual value
1
not used
2
Process actual +
2
+ (4...20 mA)
3
Process actual –
3
GND
4
not used