5 electrical connection devicenet, 16 start-up, 1 safety instructions 16.2 starting-up type 8792 – Burkert Type 8793 User Manual
Page 42: 1 specifying the standard settings

42
Start-Up
Type 8792, 8793
15.5 Electrical connection DeviceNet
To operate the appliance, the following must be connected:
→
X1 - circular connector M12, 8-pole
(operating voltage see “Tab. 18”) and
→
X3 - circular connector M12, 5-pole
(DeviceNet see “Tab. 23”).
15.5.1 X3 - M12, 5-pole circular connector -
bus connection
Pin Signal
Colour
Configuration
1
Shielding
not used
2
3
4
1
5
2
V+
not used
3
V–
not used
4
CAN H
white
5
CAN L
blue
Tab. 23: Pin assignment DeviceNet; X3 - M12, 5-pole circular connector -
bus connection
When the operating voltage is applied, Type 8792/8793 is
activated.
→
Now make the required basic settings:
Positioner:
see “16.2.1 Specifying the standard settings”
Process controller:
see “16.3.1 Basic settings of the process controller”
16 START-UP
16.1 Safety instructions
WARNING!
Risk of injury from improper operation!
Improper operation may result in injuries as well as damage to the
device and the area around it.
▶ Before start-up, ensure that the operating personnel are familiar
with and completely understand the contents of the operating
instructions.
▶ Observe the safety instructions and intended use.
▶ Only adequately trained personnel may operate the equipment/
the device.
16.2 Starting-up Type 8792
16.2.1 Specifying the standard settings
The basic settings are made on the setting level.
To change from the process to the setting level, press the
MENU
key for approx. 3 seconds.
You must make the following basic settings for starting up:
• Setting the input signal (INPUT)
• Automatic adjustment of the positioner (X.TUNE)
english