beautypg.com

13 fluid connection – Burkert Type 8793 User Manual

Page 26

background image

26

Fluid connection

Type 8792, 8793

Attach remote sensor on the actuator.
The correct procedure is described in the instructions for the
path sensor.

Connect compressed air to the Type 8793.

Connect Type 8793 pneumatically to the actuator

Switch on Type 8793 operating voltage.

To obtain the best possible control precision, adjust the path
sensor so that path to be measured corresponds to the signal
range 4 – 20 mA (only if the path sensor includes this function).

In the

ADD.FUNCTION menu activate the POS.SENSOR

function. Then select

POS.SENSOR in the main menu and set

ANALOG.
The procedure is described in the operating instructions for Type
8792/8793 in the chapter

“Starting up and operation of the

process controller / auxiliary functions / POS.SENSOR”.

Run the

X.TUNE function.

13 FLUID CONNECTION

DANGER!

Risk of injury from high pressure in the equipment!

▶ Before loosening the pneumatic lines and valves, turn off the

pressure and vent the pneumatic lines.

WARNING!

Risk of injury from improper installation!

▶ Installation may be carried out by authorized technicians only

and with the appropriate tools!

Risk of injury from unintentional activation of the system and
an uncontrolled restart!

▶ Secure system from unintentional activation.

▶ Following installation, ensure a controlled restart.

Working connection 2
(connection: A2)

Supply pressure connection
1.4 – 7 bar (connection: P)

Working connection 1 <
(connection: A1)

Deaeration connection

Fig. 16: Fluid installation / Location of the connections

english

This manual is related to the following products: