Start-Up

Type 8792, 8793

Input the input signal (INPUT)

In the

INPUT menu option select the input signal for the set-

point value.
(4 ... 20 mA, 0 ... 20 mA, 0 ... 10 V or 0 ... 5 V).

INPUT

4-20 mA

0-20 mA

0-10 V

0-5 V

Selection of the
input signal

EXIT

ENTER

SELEC

X.TUNE

press for approx. 3 s

Process level (values are displayed)

MENU

Einstellebene

ADD.FUNCTION

EXIT

Fig. 25: Operating structure INPUT; Input the signal

Automatic adjustment of the positioner to the operating
conditions (X.TUNE)

WARNING!

Danger due to the valve position changing when the X:TUNE
function is run!
When the

X.TUNE function is run under operating pressure, there

is an acute risk of injury.

Never run X.TUNE while the process is running!

▶ Secure system from unintentional activation!

NOTE!

An incorrect supply pressure or incorrectly connected
operating medium pressure may cause the controller to be
wrongly adjusted!

▶ Run X.TUNE in each case at the supply pressure available in

subsequent operation (= pneumatic auxiliary power).

• Run the

X.TUNE function preferably without operating medium

pressure to exclude interference due to flow forces.

The following functions are actuated automatically:
• Adjustment of the sensor signal to the (physical) stroke of the

actuator used.

• Determination of parameters of the PWM signals to control the

solenoid valves integrated in Type 8792/8793.

• Setting of the controller parameters of the positioner. Optimization

occurs according to the criteria of the shortest possible transient
time with simultaneous freedom from overshoot.