beautypg.com

4 connecting the process controller type 8793, English – Burkert Type 8793 User Manual

Page 32

background image

32

Electrical Installation

Type 8792, 8793

14.4 Connecting the process controller

Type 8793

First connect the process controller as described in chapter “14.3
Connection of the positioner Type 8792”
.

14.4.1 X5 - M8, 4-pole circular connector,

process actual value input

Input
type

**

Pin Configuration

DIP
switches

On the
device
side

External
circuit

4 ... 20 mA
- internally
supplied

1

(brown)* +24 V
transmitter supply

Switch
on left

1

2

3
4

Trans-
mitter

GND

2

(white)* Output from
transmitter

3

(blue)* GND (identical
with GND operating
voltage)

4

(black)* Bridge to
GND (Pin 3)

4 ... 20 mA
- externally
supplied

1

(brown)* not used

Switch
on right

2

(white)* Process
actual +

2

4 ... 20 mA

3

(blue)* not used

4

(black)*
Process actual –

4

GND
4 - 20 mA

Input
type

**

Pin Configuration

DIP
switches

On the
device
side

External
circuit

Frequency
-internally
supplied

1

(brown)* +24 V
sensor supply

Switch
on left

1

+24 V

2

(white)* Clock input

2

Clock +

3

(blue)* Clock input –
(GND)

3

Clock – /
GND (iden-
tical with
GND oper-
ating voltage)

4

(black)* not used

Frequency
- externally
supplied

1

(brown)* not used

Switch
on right

2

(white)* Clock input +

2

Clock +

3

(blue)* Clock input –

3

Clock –

4

(black)* not used

Pt 100
(***see
information)

1

(brown)* not used

Switch
on right

2

3

4

Pt 100

2

(white)* Process actual
1 (power supply)

3

(blue)* Process actual
3 (GND)

4

(black)* Process actual
2 (compensation)

* The wire colours indicated in brackets refer to the connection cable,

part no. 918718, available as an accessory.

**

Can be adjusted via software (see Operating Instructions,chapter
„Specifying the standard settings“).

Tab. 10: Pin assignment; X5 - M8, 4-pole circular connector - process

actual value input

english