4 connecting the process controller type 8793, English – Burkert Type 8793 User Manual
Page 32
32
Electrical Installation
Type 8792, 8793
14.4 Connecting the process controller
Type 8793
→
First connect the process controller as described in chapter “14.3
Connection of the positioner Type 8792”.
14.4.1 X5 - M8, 4-pole circular connector,
process actual value input
Input
type
**
Pin Configuration
DIP
switches
On the
device
side
External
circuit
4 ... 20 mA
- internally
supplied
1
(brown)* +24 V
transmitter supply
Switch
on left
1
2
3
4
Trans-
mitter
GND
2
(white)* Output from
transmitter
3
(blue)* GND (identical
with GND operating
voltage)
4
(black)* Bridge to
GND (Pin 3)
4 ... 20 mA
- externally
supplied
1
(brown)* not used
Switch
on right
2
(white)* Process
actual +
2
4 ... 20 mA
3
(blue)* not used
4
(black)*
Process actual –
4
GND
4 - 20 mA
Input
type
**
Pin Configuration
DIP
switches
On the
device
side
External
circuit
Frequency
-internally
supplied
1
(brown)* +24 V
sensor supply
Switch
on left
1
+24 V
2
(white)* Clock input
2
Clock +
3
(blue)* Clock input –
(GND)
3
Clock – /
GND (iden-
tical with
GND oper-
ating voltage)
4
(black)* not used
Frequency
- externally
supplied
1
(brown)* not used
Switch
on right
2
(white)* Clock input +
2
Clock +
3
(blue)* Clock input –
3
Clock –
4
(black)* not used
Pt 100
(***see
information)
1
(brown)* not used
Switch
on right
2
3
4
Pt 100
2
(white)* Process actual
1 (power supply)
3
(blue)* Process actual
3 (GND)
4
(black)* Process actual
2 (compensation)
* The wire colours indicated in brackets refer to the connection cable,
part no. 918718, available as an accessory.
**
Can be adjusted via software (see Operating Instructions,chapter
„Specifying the standard settings“).
Tab. 10: Pin assignment; X5 - M8, 4-pole circular connector - process
actual value input
english