7 pneumatic data – Burkert Type 8793 User Manual
Page 12
12
Technical Data
Type 8792, 8793
Pt 100:
Measuring range -20 ... +220 °C
Resolution
< 0,1 °C
Measurement current < 1 mA
Input data for set-point value signal
0/4 ... 20 mA:
Input resistance 180 Ω
Resolution
12 bit
0 ... 5/10 V:
Input resistance 19 kΩ
Resolution
12 bit
Analogue feedback
max. current
10 mA
(for voltage output 0 ... 5/10 V)
Burden (load)
0 ... 560 Ω
(for voltage output 0/4 ... 20 mA)
Inductive proximity
switches
100 mA current limit
Binary outputs
galvanically isolated
Current limiting
100 mA, output is clocked if overload
occurs
Binary input
galvanically isolated
0 ... 5 V = log „0“, 10 ... 30 V = log „1“
inverted input in reverse order
(input current < 6 mA)
7.7 Pneumatic data
Control medium
Quality classes in accordance with DIN ISO
8573-1
Dust content
Class 5, max. particle size 40 µm, max. par-
ticle density 10 mg/m³
Water content
Class 3, max. pressure dew point - 20 °C or
min. 10 degrees below the lowest operating
temperature
Oil content
Class 5, max. 25 mg/m³
Temperature range
of compressed air
0 ... +60 °C
Pressure range
1.4 – 7 bar
Air flow rate
95 l
N
/ min (at 1.4 bar*) for aeration and
deaeration
150 l
N
/ min (at 6 bar*) for aeration and
deaeration
(Q
Nn
= 100 l
N
/ min (according to definition for
pressure drop from 7 to 6 bar absolute)).
Connections
Internal thread G1/4“
* Pressure specifications: Overpressure with respect to
atmospheric pressure
english