4 electrical connection profibus – Burkert Type 8793 User Manual
Page 41
41
PROFIBUS DP / DeviceNet
Type 8792, 8793
15.3.3 X4 - M8, 4-pole socket, optional -
remote sensor (for remote model only)
Connection of the digital, contact-free position sensor
Type 8798:
Pin Configuration
On the
device
side
External circuit
1
Supply sensor +
S +
+
Remote
Sensor
Type
8798
digital
2
Supply sensor –
S –
–
3
Serial interface, A-line A
A-line
4
Serial interface, B-line B
B-line
Tab. 20: Plug assignments PROFIBUS DP / DeviceNet; X4 - M8, 4-pole
socket - digital, contact-free position sensor Type 8798
Connection of an analog, potentiometric position sensor:
Pin Configuration
On the device
side
External circuit
1
Potentiometer 1 1
Potentio-
meter
2
Center tap 2
2
3
Potentiometer 3 3
4
not used
Tab. 21: Plug assignments PROFIBUS DP / DeviceNet; X4 - M8, 4-pole
socket - analog, potentiometric position sensor
15.4 Electrical connection PROFIBUS
To operate the appliance, the following must be connected:
→
X1 - circular connector M12, 8-pole
(operating voltage see “Tab. 18”) and
→
X2 - socket M12, 5-pole, inversely coded
(PROFIBUS DP see “Tab. 22”).
15.4.1 X2/X3 - M12, 5-pole socket/circular
connector - bus connection
Pin Configuration External circuit / Signal level
1
VP+5
Supply the terminating resistors
2
RxD/TxD-N
Received/transmitted data -N, A-line
3
DGND
Data transmission potential (earth to 5 V)
4
RxD/TxD-P
Received/transmitted data -P, B-line
5
Shielding
Shielding / protective earth
Tab. 22: Pin assignment PROFIBUS DP;
X2/X3 - M12, 5-pole circular connector/socket - bus connection,
PROFIBUS DP
When the operating voltage is applied, Type 8792/8793 is
activated.
→
Now make the required basic settings:
Positioner:
see “16.2.1 Specifying the standard settings”
Process controller:
see “16.3.1 Basic settings of the process controller”
english