Electrical Installation
Type 8792, 8793
14.6.2 Output signals to the control centre
(e.g. PLC)
(required for analogue output and/or
binary output option only)
→
Connect terminals according to the model (options) of the
positioner.
Terminal Configuration
On the device
side
External circuit / Signal level
83 +
Binary output
1
83 +
24 V / 0 V, NC / NO
specific to operating voltage
GND (terminal GND)
85 +
Binary output
2
85 +
24 V / 0 V, NC / NO
specific to operating voltage
GND (terminal GND)
31 +
Analogue
feedback +
31 +
+ (0/4 ... 20 mA or 0 ... 5 / 10 V)
completely galvanically isolated
32 –
Analogue
feedback
GND
32 –
GND Analogue feedback
Tab. 12: Terminal assignment; output signals to the control centre
14.6.3 Operating voltage
Terminal Configuration
On the device
side
External circuit /
Signal level
+24 V
Operating voltage + +24 V
GND
24 V DC ± 10 %
max.
residual ripple
10 %
GND
Operating voltage
GND
Tab. 13: Terminal configuration; operating voltage
14.6.4 Terminal assignment for external
position sensor (for remote model
only)
Connection of the digital, contact-free position sensor
Type 8798:
Terminal Configuration
On the
device side
External circuit / Signal level
S +
Supply sensor
+
S +
+
Remote
Sensor
Type
8798*
For
assignment
of the wire
color see
“Tab. 15”
S –
Supply sensor
–
S –
–
A
Serial interface
A-line
A
A-line
B
Serial interface
B-line
B
B-line
Tab. 14: Terminal configuration; position sensor Type 8798
Positioner
Terminal
Wire color Type 8798
Cable type 1
Cable type 2
S +
brown
brown
S –
white
black
A
green
red
B
yellow
orange
Tab. 15: Assignment of the wire color, position sensor Type 8798
english