Electrical Installation
Type 8792, 8793
Input
type*
Terminal Configuration
On the
device side
External
circuit
Frequency
-internally
supplied
actual value
1
+24 V sensor supply
1
+24 V
2
Clock input +
2
Clock +
3
not used
4
Clock input –
4
GND
GND from operating
voltage
GND
Clock
– (GND)
Frequency
- externally
supplied
actual value
1
not used
2
Clock input +
2
Clock +
3
not used
4
Clock input –
4
Clock –
Pt 100
see infor-
mation**
actual value
1
not used
2
3
4
Pt 100
2
Process actual 1
(Power supply)
3
Process actual 3
(GND)
4
Process actual 2
(Compensation)
*
Can be adjusted via software
(see Operating Instructions,chapter „Specifying the standard settings“)..
Tab. 17: Terminal assignments of the process actual value input
** Connect the Pt 100 sensor via 3 cables for cable com-
pensation reasons.
It is essential to bridge Pin 3 and Pin 4 on the sensor.
When the operating voltage is applied, the process controller is
operating.
→
Now make the required basic settings and actuate the automatic
adjustment of the process controller. The procedure is described
in chapter “16.3 Start-up Type 8793”.