beautypg.com

Burkert Type 8793 User Manual

Page 22

background image

22

Attachment and assembly

Type 8792, 8793

WARNING!

Risk of injury from improper installation!

▶ Installation may be carried out by authorised technicians only

and with the appropriate tools!

Risk of injury from unintentional activation of the system and
an uncontrolled restart!

▶ Secure system from unintentional activation.

▶ Following assembly, ensure a controlled restart.

Procedure:

Specify the attachment position of the Type 8792/8793:
- parallel to the actuator or
- rotated by 90° to the actuator.

Determine home position and direction of rotation of the
actuator.

Connect adapter to the shaft of the Type 8792/8793 and secure
with 2 setscrews.

Anti-twist safeguard:
Note the flat side of the shaft!
One of the setscrews must be situated on the flat side of the
shaft as an anti-twist safeguard (see “Fig. 12”).
Rotation range of the position sensor:
The maximum ratation range of the position sensor is 180°.
The shaft of the Type 8792/8793 may be moved within this
range only.

90°

Ideal position

for the swing range

of the flattened shaft.

(min. 30 ° / max. 180 °)

The swing movement of the flattened
shaft must be within the position
sensor turning range of 180°.

Flattened shaft

180°

Maximum

swing range

Fig. 12: Rotation range / anti-twist safeguard

Assemble the multi-part assembly bridge* suitable for the
actuator.

Attach the assembly bridge to the Type 8792/8793 using
4 cheese-head screws

and circlips

(see “Fig. 13”).

english

This manual is related to the following products: