Burkert Type 8644 User Manual
Page 90
86 - 8644/phoenix
S
YSTEM
D
ESCRIPTION
Parameter error on the PROFIBUS (CHK_CFG-Telegram)
Type No.
Cause of error
Resolution
2
7
The length code of the configured AirLine
terminal does not match the length code of
the terminal in the station.
Ascertain the precise location of the error
with the aid of the device-specific diagnosis
in your control.
Check the configuration in the hardware
configurator.
8
The number of manufacturer-specific data
from the special ID format of the AirLine
terminal contains errors. The number is 2,
3 or a multiple of 2.
Ascertain the precise location of the error
with the aid of the device-specific diagnosis
in your control.
9
Too few output process data for the AirLine
terminal were configured inside the ID
format.
Ascertain the precise location of the error
with the aid of the device-specific diagnosis
in your control.
10
Too few input process data for the AirLine
terminal were configured inside the ID
format.
Ascertain the precise location of the error
with the aid of the device-specific diagnosis
in your control.
11
More than 244 bytes are required for
configuration of the PROFIBUS.
12
An internal list is too short.
13
Too few output bytes configured for de-
activated terminals.
Ascertain the precise location of the error
with the aid of the device-specific diagnosis
in your control.
14
Too few input bytes configured for de-
activated terminals.
Ascertain the precise location of the error
with the aid of the device-specific diagnosis
in your control.