Burkert Type 8644 User Manual
Page 127
8644/phoenix - 123
S
YSTEM
D
ESCRIPTION
Limitations for use in Zone 2
ATTENTION!
For valve types 6526 and 6527, for use in Zone 2 with temperature class T4, the limitation
(valve switch-off time)
T
OFF
≥≥≥≥≥
0.2 s must be strictly complied with under the following
conditions:
•
with fast switch-on cycles (valve switch-on time
T
ON
< 3 s)
•
maximum ambient temperature of 55° C
•
maximum permissible overvoltage U
nom
+ 10 %
T
OFF
T
ON
Valve switching time
If the valve is switched on for longer than 3 s, there are
no limitations for the time until the next switch-on
of the valve.