Error description – Burkert Type 8644 User Manual
Page 89
8644/phoenix - 85
S
YSTEM
D
ESCRIPTION
Error description
Parameter error on the PROFIBUS (SET_PRM-Telegram)
Type No.
Cause of error
Resolution
1
1
An incorrect terminal number is being
used.
Check whether the terminal is
parameterizable.
2
A parameter block is incomplete.
The number of terminals and parameter
blocks does not match.
3
The data length of the parameter block is
too small.
Check the number of parameters.
4
The data length of the parameter block is
too big.
Check the number of parameters.
5
The internal block for configuration,
security value and PCP is too small.
Check the configuration of the parameters
for the terminals.
6
Header byte of the module parameter is
not correct.
Check the first byte of the module
parameters.
7
PCP initialisation of a terminal that has no
PCP functionality.
Check the planning.
8
Too many data blocks for the terminal.
The number of terminals and parameter
blocks does not match.
9
Incomplete data block in a de-activated
terminal.
Check the number of parameters.
Parameter error on the PROFIBUS (CHK_CFG-Telegram)
Type No.
Cause of error
Resolution
2
1
Fewer AirLine terminals were configured
than are present in the station.
Add the terminals in the configuration.
2
More AirLine terminals were configured
than are present in the station.
Delete the superfluous terminals from your
configuration or add the missing terminals
to the station.
3
The first byte of the special ID format of
the AirLine terminal contains errors.
Ascertain the precise location of the error
with the aid of the device-specific diagnosis
in your control.
4
Too few bytes from the special ID format
for the last AirLine terminal configured.
Check the ID format.
5
The sum of configured process data for
inputs and outputs on the station is greater
than 184 bytes (DIP8=OFF) or 176 bytes
(DIP8=ON).
Bring together serveral AirLine terminals in
the configuration so that the process data
become compressed (fewer empty bits).
6
The ID code of the configuration does not
match that of the AirLine terminal.
Ascertain the precise location of the error
with the aid of the device-specific diagnosis
in your control. Check the configuration in
the hardware configurator.