Burkert Type 8644 User Manual
Page 45
8644/phoenix - 41
S
YSTEM
D
ESCRIPTION
Error codes during DPV1 communication
If there is an error present during DPV1 or PD-PCP communication in relation to an E/A module, this is
displayed via 0x44 on byte 2 of the data block.
DPV1 error:
Function_Num = 0xDE (Error Read) or 0xDF (Error Write)
Error_Decode = 0x80 (DPV1 communication)
Error codes during DPV1 communication
ATTENTION!
Error codes during DPV1 communication are errors in relation to DPV1/PCP.
During DPV1 communication you will find the error code on byte 3, during communication
in the process data channel, error code 1 is located on byte 2 of the response.
Pay attention to the individual displays in your working environment at all times.
Error_Code_1
Error_Code_2
Comment
0xA0
0
Object from the field bus module cannot be read.
0xA1
0
Object from the field bus module cannot be written.
0xB0
0
wrong index from the field bus module
0xB1
0
The PB-PDU length is too small.
0xB2
0
wrong slot
0xB5
0
Module is busy.
0xB7
0
Error while writing on index 47 or 48
0xD1
0
no PCP connection
0xD2
0
Module has no PCP
0xD3
0
Timeout from module
0xD4
0
wrong service
0xD5
0
VC1 sequence not correct
0xD6
0
VC1 length incorrect
0xF..
Error while writing module parameter
0xF1
0
An incorrect module number was used.
0xF2
0
The parameter block is incomplete.
0xF3
0
The data length of the parameter block is too small.
0xF4
0
The data length of the parameter block is too big.
0xF5
0
The internal block for configuration, security value and
PCP is too small.
0xF6
0
Header byte from the module parameter block is not
correct.
0xF7
0
PCP initialisation for a module that has no PCP
functionality.
0xF8
0
too many data blocks for the module