28 - 8644/phoenix

S

YSTEM

D

ESCRIPTION

POWER LOSS

Formula for calculation of the power loss of the electronics

P

EL

= P

Bus

+ P

Peri

Substituting the maximum currents of 2 A (logic) and 0.5 A (for analog terminals) in the formula for
calculation of the power loss with periphery connected, we obtain:

P

PERI

= 2.2 W + 0.35 W = 2.55 W

This 2.55 W corresponds to 100 % network loading capacity in the derating curves.

Derating

ATTENTION!

Make sure that at an ambient temperature above 40 °C, the nominal loading capacity
given by the derating curves is not exceeded. As can be seen from the formula, the total
loading with attached periphery (P

PERI

) is the relevant quantity. If for example no current is

consumed by the analog supply, the fraction of the current from the logic supply may be
greater.

Where

P

EL

Total power loss in the terminal

P

BUS

Power loss for bus operation without peripheral loading (constant)

P

PERI

Power loss with periphery connected

I

LN

Current consumption of participant

n from logic supply

n

Index designating the number of participants connected (n = 1 to a)

a

Number of participants connected (supply with logic voltage)

Σ

I

Ln

Sum of all current consumed by participants from the 7.5 V logic supply (max. 2 A)

I

LM

Current consumption of participant

m from analog supply

m

Index designating the number of nalog participants connected (m = 1 to b)

b

Number of analog participants connected (supply with analog voltage)

Σ

I

Lm

Sum of all current consumed by participants from the 24 V analog supply (max. 0.5 A)

a

n=0

b

m=0

W

A

W

A

P

EL

= 2,6 W + (1,1 x

Σ

Σ

Σ

Σ

Σ

ΙΙΙΙΙ

Ln

) + (0,7 x

Σ

Σ

Σ

Σ

Σ

ΙΙΙΙΙ

Lm

)

a

b

n=0

m=0