The pressure measurement module is controlled via 2 bytes of input data and 2 bytes of output data.

The first byte is the control byte of the output data (master) and the status byte of the input data (master).
In normal operation the status byte corresponds to the response of the control byte of the previous
interrogation.

The second byte is the data byte.

Master

PMM

data byte (2)

data byte (2)

control byte (1)

control byte (1)

Control byte

The difference between the process and parametrization data is determined by the status bit of the control
byte.

Status bit 0

process cata

Status bit 1

parametrization data

Process data

Process data transmits the pressure value

1)

of the system and the units set up in the module.

Calling up process data

When you call up process data, the control byte must assume a value between 0x00 and 0x7F
(status bit = 0). The data byte is not taken into account.

The status byte of the response depends on the unit set on the local display.
The data byte supplies the pressure value

1)

.

Unit

Status byte

on display

of response

bar

0x38

kPa

0x39

psi

0x3A

1)

Pressure value: value in bar x 10 (without decimal point)

Structure of the control byte

AS:

status bit (process or parametrization data)

FB:

error bit

15-10: bits containing further information

AS

FB

15

14

13

12

11

10