Burkert Type 8644 User Manual
Page 35
8644/phoenix - 31
S
YSTEM
D
ESCRIPTION
Connection technique
Tension spring terminals
Recommended cable lengths
max. 30 m;
cable routing over free areas not permissible
Forwarding
Via potential shunting
Behaviour on voltage drop and
The voltages forwarded from the bus
interruption
terminal to the potential shunters (main and segment
voltage) follow the appliedsupply voltages without delay.
Rated voltage
24 V DC
Tolerance
- 15 % / + 20 % (to EN 61131-2)
Ripple
± 5 %
Permissible range
19.2 V to 30 V
Current loading
Max. 8 A
Technical data of the field bus module Profibus DP bus node
ATTENTION!
Protect 24 V section externally!
This 24 V section must be protected externally with a fuse. The power supply unit must be
capable of supplying 4 times the rated current, so that in case of a fault, blowing of the
fuse is assured.
Minimize heat generation!
For supplying the main voltage and for supplying or tapping the segment voltage, use both
adjacent contacts.
Observe current carrying capacity!
The maximum cumulative current through the potential shunter is 8 A.
Min. current consumption at rated voltage
0.10 A DC
main power supply
(at open circuit, i.e. incoming remote bus attached, no local
bus participants connected, bus inactive)
Max. current consumption at rated voltage
1.25 A DC
main power supply
consisting of:
0.75 A DC for logic supply
0.5 A DC for analog voltage supply
Protective features
Overvoltage
yes
False polarity
yes